Rolling average – Yokogawa Touch Screen GP20 User Manual

Page 65

Advertising
background image

1-51

IM 04L51B01-01EN

Configuring the GX/GP

1

2

3

4

5

App

Reset

To reset the TLOG computed value at each interval, select

On.

The figure below illustrates the reset operation of sum computation (TLOG.SUM).

Example: Result of the TLOG.SUM computation

When reset is

On, the sum value is computed over each interval. When set to Off, the sum

value from computation start is computed.

1

2

3

Reset

Reset

Reset

Reset: On

Timer timeout

Reset: Off

Rolling average

Setup Item

Selectable Range or Options

Default Value

On/Off

Off, On

Off

Interval

1

1s, 2s, 3s, 4s, 5s, 6s, 10s, 12s, 15s, 20s, 30s,

1min, 2min, 3min, 4min, 5min, 6,in, 10min,

12min, 15min, 20min, 30min, 1h

10s

Number of samples

1

1 to 1500

1

1 Appears when rolling average is

On.

On/Off

Set this to

On to perform rolling average.

Interval

Set the sampling interval for performing rolling average. The sampling interval takes on a

value that is an integer multiple of the scan interval. For example, if the sampling interval is

set to 5 s when the scan interval is 2 s, the actual sampling interval is 6 s.

Number of samples

Set the number of samples for performing rolling average.

The rolling average time is equal to the sampling interval × the number of samples.

Note

• If the number of data points to be averaged has not reached the specified number of samples

immediately after computation is started, the average of the available data is computed.

• Computation error data is excluded from the rolling average computation.

• If the computed data exceeds the upper or lower limit, the data is clipped at the upper or lower

limit, and the rolling average is computed. The upper and lower limits are “±100000000” ignoring

the decimal point. The decimal place is the same as that of the span lower limit.

1.5 Configuring Math Channels

Advertising
This manual is related to the following products: