I/o channel data status information – Yokogawa Touch Screen GP20 User Manual

Page 351

Advertising
background image

4-31

IM 04L51B01-01EN

Using Modbus Functions (Communicating with Modbus devices)

1

2

3

4

5

App

I/O Channel Data Status Information

I/O Channel Data

Hold Register

Data Type

Channel 0001 status information

404501

16-bit signed integer

|

|

Channel 0010 status information

404510

Channel 0101 status information

404511

|

|

Channel 0110 status information

404520

Channel 0201 status information

404521

|

|

Channel 0210 status information

404530

Channel 0301 status information

404531

|

|

Channel 0310 status information

404540

Channel 0401 status information

404541

|

|

Channel 0410 status information

404550

Channel 0501 status information

404551

|

|

Channel 0510 status information

404560

Channel 0601 status information

404561

|

|

Channel 0610 status information

404570

Channel 0701 status information

404571

|

|

Channel 0710 status information

404580

Channel 0801 status information

404581

|

|

Channel 0810 status information

404590

Channel 0901 status information

404591

|

|

Channel 0910 status information

404600

• There is no decimal place information.

Error code

Meaning

0

No error

1

Skip

2

+Over

3

–Over

4

+Burnout

5

–Burnout

6

A/D error

7

Invalid data

16

Computation error

17

Communication error

5 bits

4 bits

Status information

Alarm list

0

Reserved

area

Error code

RJC error

A/D calibration

value error

0 0 0 0

Level 1

Level 2

Level 3

Level 4

2 bytes

Higher Lower

4.5 Modbus Function and Register Assignments