Communication Operation

Communication ports are closed when a power failure occurs.

• Reestablish Ethernet connections.

• Client function

• When Modbus client is in use and a power failure occurs in the middle of a

transmission, the data will not be retransmitted.

• When the FTP client function is in use and a power failure occurs in the middle of a file

transfer, the file will be re-transferred when the GX/GP recovers.

• Communication channel values are retained even during a power failure. The GX/GP can

be configured so that the values take on preset values when the GX/GP recovers.

DO Operation

DO output values are not retained during a power failure.

• Alarm output

Alarms are set to off when the GX/GP recovers.

• Manual DO operation

Manual DO operation is set to off, regardless of the condition before the power failure.

Power Recovery Operation Summary

Operation

Function

Held/Not Held Description

Recording

Recording status

Held

If a power failure occurs during recording,

recording will continue when the GX /GP

recovers.

File creation

Held

A power failure divides files.

Trend

waveform

File type: Event data

only

Not held

Waveforms before the power failure will be

lost.

Trend rate switching

Not held

Waveforms before the power failure will be

lost.

Other than those above Held

Continues to be displayed.

Timer

Relative timer

Held

Timers do not count during the power failure

period.

Absolute timer

Match time timer

Held

If timers expire during a power failure,

timeout processing occurs when the GX/GP

recovers.

Remote

Remote condition

Held

If remote conditions change during a power

failure, the corresponding actions are

executed when the GX/GP recovers.

AI channel

Moving average

Not held

When the GX/GP recovers, a new moving

average will start.

Computation

Computation condition

Held

If a power failure occurs during computing,

computing will continue when the GX/GP

recovers.

Computed results

Held

Data before the power failure is retained.

Rolling average

Held

Average values before the power failure is

retained.

TLOG Computation

Held

If absolute timers or match time timers

expire during a power failure, TLOG

computation is performed when the GX/GP

recovers.

Communication Connection

Not held

Connections need to be reestablished when

the GX/GP recovers.

Client

Not held

Modbus: Data in transmission is discarded.

FTP: Files in transmission is retransmitted.

Communication channel Held

Data before the power failure is retained.

DO

Alarm

Not held

Set to off.

Manual DO

Not held

Set to off.

Appendix 5 Power Recovery Operation