App-24
IM 04L51B01-01EN
Communication Operation
Communication ports are closed when a power failure occurs.
• Reestablish Ethernet connections.
• Client function
• When Modbus client is in use and a power failure occurs in the middle of a
transmission, the data will not be retransmitted.
• When the FTP client function is in use and a power failure occurs in the middle of a file
transfer, the file will be re-transferred when the GX/GP recovers.
• Communication channel values are retained even during a power failure. The GX/GP can
be configured so that the values take on preset values when the GX/GP recovers.
DO Operation
DO output values are not retained during a power failure.
• Alarm output
Alarms are set to off when the GX/GP recovers.
• Manual DO operation
Manual DO operation is set to off, regardless of the condition before the power failure.
Power Recovery Operation Summary
Operation
Function
Held/Not Held Description
Recording
Recording status
Held
If a power failure occurs during recording,
recording will continue when the GX /GP
recovers.
File creation
Held
A power failure divides files.
Trend
waveform
File type: Event data
only
Not held
Waveforms before the power failure will be
lost.
Trend rate switching
Not held
Waveforms before the power failure will be
lost.
Other than those above Held
Continues to be displayed.
Timer
Relative timer
Held
Timers do not count during the power failure
period.
Absolute timer
Match time timer
Held
If timers expire during a power failure,
timeout processing occurs when the GX/GP
recovers.
Remote
Remote condition
Held
If remote conditions change during a power
failure, the corresponding actions are
executed when the GX/GP recovers.
AI channel
Moving average
Not held
When the GX/GP recovers, a new moving
average will start.
Computation
Computation condition
Held
If a power failure occurs during computing,
computing will continue when the GX/GP
recovers.
Computed results
Held
Data before the power failure is retained.
Rolling average
Held
Average values before the power failure is
retained.
TLOG Computation
Held
If absolute timers or match time timers
expire during a power failure, TLOG
computation is performed when the GX/GP
recovers.
Communication Connection
Not held
Connections need to be reestablished when
the GX/GP recovers.
Client
Not held
Modbus: Data in transmission is discarded.
FTP: Files in transmission is retransmitted.
Communication channel Held
Data before the power failure is retained.
DO
Alarm
Not held
Set to off.
Manual DO
Not held
Set to off.
Appendix 5 Power Recovery Operation