2-8

IM 04L51B01-01EN

2.1.5

Clearing Computation Data Dropout Displays

You can carry out this procedure when a computation data dropout occurs. When a

computation data dropout occurs, the math icon turns yellow.

Procedure

1

Press

MENU.

The menu screen appears.

2

Tap

Computing.

The computation operation screen appears.

3

Tap

ACK.

The math icon turns gray.

ACK on the computation operation screen is valid only when a computation data dropout

occurs.

Operation complete

Note

A computation data dropout occurs if the computation is not completed within the scan interval. If

computation data dropout occurs frequently, reduce the load on the CPU by reducing the number

of math channels or setting a longer scan interval. When a computation data dropout occurs during

recording, the computed data of the scan interval in which the dropout occurred is set to the data

immediately before the dropout.

2.1 Starting and Stopping Recording and Computation