4.5 Modbus Function and Register Assignments

4.5.1

Modbus Client/Master Function

Function

The GX/GP supports the following functions.

The server (slave) must support these functions.

Function Code Function

Operation

1

Read the coil status

(0xxxx)

The GX/GP reads the coil status of the server (slave)

device.

2

Read the input relay

status (1xxxx, 1xxxxx)

The GX/GP reads the input relay status of the server

(slave) device.

3

Read the hold register

(4XXXX, 4XXXXX)

The GX/GP reads the hold register of the server

(slave)

into a communication channel.

4

Read the input register

(3XXXX, 3XXXXX)

The GX/GP reads the input register of the server

(slave)

into a communication channel.

5

Change the single coil

status

(0xxxx)

The GX/GP changes the single coil status of the server

(slave) device (off/on).

6

Write to a single hold

register (4xxxx, 4xxxxx)

The GX/GP writes to a single hold register of the server

(slave)

.

15

Change the coil status

(0xxxx)

The GX/GP changes the coil status of the server (slave)

device (off/on).

16

Write to the hold register

(4XXXX, 4XXXXX)

The GX/GP writes the I/O channel data, math channel

data, or communication channel data to the hold register

of the server (slave).

Command

Command type: Read, Write

Number of commands: GX20/GP20: Set up to 100 commands

GX10/GP10: Set up to 50 commands

Data type: See the table below.

Symbol

Description

INT16

16-bit signed integer

UINT16

16-bit unsigned integer

INT32_B

32-bit signed integer (big endian)

INT32_L

32-bit signed integer (little endian)

UINT32_B

32-bit unsigned integer (big endian)

UINT32_L

32-bit unsigned integer (little endian)

FLOAT_B

32-bit floating point (big endian)

FLOAT_L

32-bit floating point (little endian)

BIT

Bit

Special value output

When a register is read or when its content is exported through the Modbus function, the

GX/GP may output the following special values.

Channel status

Data type

Integer

Floating

+Over, +Burnout

Maximum expressible value

+∞

–Over, –Burnout

Minimum expressible value

–∞

Example: Channel status is “–Over”

Data type

Output value

INT16

–32768 (0x8000)

INT32

–2147483648 (0x80000000)

FLOAT

–∞ (0xff800000)