Alarm delay – Yokogawa Touch Screen GP20 User Manual

Page 33

Advertising
background image

1-19

IM 04L51B01-01EN

Configuring the GX/GP

1

2

3

4

5

App

Hysteresis

Set this to establish an offset between the value used to activate and release alarms.

This is fixed at 0 for the

DI range.

Example:

H: If you set the alarm value of a high limit alarm to 1.0000 V and the hysteresis to 0.0005 V,

an alarm is activated when the measured value is greater than or equal to 1.0000 V and is

released when the measured value is less than or equal to 0.9995 V.

Logging

Set this

On to display an alarm (notify you) when an alarm occurs. If set to Off, when an

alarm occurs, the GX/GP outputs signals to alarm output DO channels or internal switches

but does not display the alarm. Alarms are also not recorded in the alarm summary.

Output type

Set the alarm output destination.

Alarm status can be output to the the relay (DO channel) or internal switches (100 software

switches). Internal switch values are shown below. Like the DO output relay, you can specify

AND/OR operation.

Alarm

Alarm occurrence

Alarm release

Internal switch

1

0

Internal switches can be used as events of the event action function (see page 1-108 in section

1.14, “Configuring the Event Action Function”). In addition, they can also be written in

calculation expressions of math channels (/MT option).

Output No.

Set the number of the relay (DO channel) or internal switch to output alarms to.

Alarm delay

1

Setup Item

Selectable Range or Options

Default Value

Hour

1 to 24

0

Minute

0 to 59

0

Second

0 to 59

10

1 Appears when Level 1, Level 2, Level 3, or Level 4 is

On.

Hour, Minute, and Second

Set the alarm delay. These values are valid when the delay high limit or delay low limit is in

use.

1.2 Configuring AI Channels (Analog input (including DI) channels)