Alarm delay (for delay high/low limit alarms) – Yokogawa Touch Screen GP20 User Manual

Page 52

Advertising
background image

1-38

IM 04L51B01-01EN

Type

Set the alarm type.

For details, see page 1-17 in section 1.2.2, “Setting Alarms”.

Alarms of channels set to difference calculation are set in the position shown in the figure

below.

Input value

Measured value on the reference channel

H, L, T, t

R, r, h, l

Measured value

Value

Set the alarm value for the specified alarm type.

For details, see page 1-17 in section 1.2.2, “Setting Alarms”.

Hysteresis

Fixed to 0.

Logging

Set this

On to display an alarm (notify you) when an alarm occurs. If set to Off, when an

alarm occurs, the GX/GP outputs signals to alarm output DO channels or internal switches

but does not display the alarm. Alarms are also not recorded in the alarm summary.

Output type

Set the alarm output destination.

Output No.

Set the number of the DO channel or internal switch to output alarms to.

Alarm delay (for delay high/low limit alarms)

Setup Item

Selectable Range or Options

Default Value

Hour

1 to 24

0

Minute

0 to 59

0

Second

0 to 59

10

Hour, Minute, and Second

Set the alarm delay. These values are valid when the delay high limit or delay low limit is in

use.