Modbus client connect limits function, 1 to 10 – Yokogawa Touch Screen GP20 User Manual

Page 150

Advertising
background image

1-136

IM 04L51B01-01EN

1.16.8 Limiting the Connection to the Modbus Server (GX/GP)

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu Communication (Ethernet)

settings > Server settings > Allowed Modbus clients

Web browser:

Config. tab > Communication (Ethernet) settings > Allowed Modbus

clients

Hardware configurator:

Communication (Ethernet) settings > Allowed Modbus clients

Description

Modbus client connect limits function

Setup Item

Selectable Range or Options

Default Value

On/Off

Off, On

Off

On/Off

Set this to

On to limit the IP addresses that can connect to the GX/GP Modbus server

function. IP addresses other than those specified here will not be able to connect. To not

limit connections, set this to

Off.

1 to 10

Setup Item

Selectable Range or Options

Default Value

On/Off

Off, On

Off

IP Address

Numerical value (0.0.0.0 to 255.255.255.255) 0.0.0.0

On/Off

Set this to

On to limit connections. You can register up to 10 IP addresses.

IP Address

Set the IP addresses to allow connection (0.0.0.0 to 255.255.255.255). You cannot specify

host names.

1.16.9 Setting the Server Functions to Use (FTP, HTTP, SNTP, MODBUS, GENE)

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu Communication (Ethernet)

settings > Server settings > Server list

Web browser:

Config. tab > Communication (Ethernet) settings > Server list

Hardware configurator:

Communication (Ethernet) settings > Server list

Description

FTP

Setup Item

Selectable Range or Options

Default Value

On/Off

On, Off

On

Port number

Numeric value (1 to 65535)

21

On/Off

Select

On to use the FTP server function.

Port number

Set the port number of the FTP server. Unless specified otherwise, you do not need to

change this number.

1.16 Configuring the Ethernet Communication Function