4 setting the a/d integral time, Setting the a/d integral time -77, App 1.7.4 setting the a/d integral time – Yokogawa Touch Screen GP20 User Manual

Page 91

Advertising
background image

1-77

IM 04L51B01-01EN

Configuring the GX/GP

1

2

3

4

5

App

1.7.4

Setting the A/D Integral Time

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu Measurement settings >

Module settings

Select module > Module 0 to 9

1

Web browser:

Config. tab > Measurement settings > Module settings

Hardware configurator:

Measurement settings > Module settings

1 The module numbers that appear depend on the GX/GP module configuration.

Description

A/D integrate

Setup Item

Selectable Range or Options

Default Value

A/D integrate

Auto, 50Hz, 60Hz, Common

2

Auto

2

Common appears when the scan interval is 500 ms or longer.

A/D integrate

Set the module’s A/D integration time. The available options appear depending on the scan

interval setting.

Options

Description

Auto

• The GX/GP automatically detects the power supply frequency and sets the

A/D integration time to 16.67 ms for 60 Hz and 20 ms for 50 Hz.

However, if the module operation mode is 10ch and the scan interval is 100 ms

or 200 ms, the A/D integration time is fixed at 1.67 ms.

• If you are using the 24 VDC power supply on models with the 24 VDC/AC

power supply (/P1 option), the A/D integration time is fixed to 20 ms

(50 Hz).

50Hz

Sets the integration time to 20 ms.

60Hz

Sets the integration time to 16.67 ms.

Common

Sets the integration time to 16.67ms, 36.67 ms or 100 ms.

Integration time and scan interval by module

Type

Integration time

Scan interval

10ch Normal

mode

2ch Only, Low

noise mode

Semi conducor

scanner

36.67ms

1s or more

100ms

2s or 5s

Electromagnetic

relay scanner

36.67ms

2s

100ms

5s

Explanation

Integration Time of the A/D Converter

The GX/GP uses an A/D converter to convert sampled analog signals to digital signals. By

setting the integration time of the A/D converter to match the time period corresponding

to one cycle of the power supply or an integer multiple of one cycle, the power supply

frequency noise can be effectively eliminated.

Common (36.67 ms/100 ms) can specified to effectively eliminate power supply frequency

noise for both 50 Hz and 60 Hz.

1.7 Setting Measurement Conditions (Scan interval, A/D integrate, etc.)

Advertising
This manual is related to the following products: