Yokogawa Touch Screen GP20 User Manual

Page 44

Advertising
background image

1-30

IM 04L51B01-01EN

Explanation

Common Display Items
Screen Configuration

The screen consists of the status display section and the data display section.

Status display section

Data display section

• Status Display Section
The status display section shows the display name, date/time, batch name (when using

the batch function), user name (when using the login function), usage of the internal

memory or SD memory card, alarm occurrence, computation status (/MT option), and

usage of operation lock or e-mail transmission.

• Data Display Section
The data display section shows the measured data using waveforms, numeric values,

and bar graphs.

Group Display

On the trend, digital, and bar graph displays, the data of channels is displayed in groups that

are set in advance.

Groups are shared among the trend, digital, and bar graph displays.

The displayed group can be switched automatically at a specified time interval (5 s to 1 min).
Number of Groups That Can Be Registered

GX20/GP20: 50 groups

GX10/GP10: 30 groups
Number of Channels That Can Be Assigned to a Group

GX20/GP20: Up to 20

GX10/GP10: Up to 10

Update Interval of Measured Values

Values are updated every 0.5 seconds. However, if the scan interval is greater than 1 s,

values are updated at the scan interval.

Alarm Indication

Alarms that are set for each channel are checked at all times and are indicated with the

symbol representing the alarm type on each display.

Alarm Type

Symbol

Alarm Type

Symbol

High limit alarm

H

High limit on rate-of-change alarm

R

Low limit alarm

L

Low limit on rate-of-change alarm

r

Difference high limit alarm h

Delay high limit alarm

T

Difference low limit alarm

l (lowercase L)

Delay low limit alarm

t

1.2 Configuring AI Channels (Analog input (including DI) channels)