Sntp log – Yokogawa Touch Screen GP20 User Manual
Page 230

2-46
IM 04L51B01-01EN
Communication Type
Description
R
Read command
W
Write command
N
Other
SNTP Log
Error code
Date and time
Scroll
Drag or flick
to scroll
Error Code
Description
ELINK
The Ethernet cable is not connected. Check the GX/GP Ethernet cable
connection.
EDORMANT
An internal processing error occurred. Contact your nearest
YOKOGAWA dealer.
EHOSTNAME
The SNTP server host name is invalid. Check the GX/GP Ethernet cable
connection, IP address setting, and SNTP server address setting.
ETCPIP
An internal processing error occurred. Contact your nearest YOKOGAWA
dealer.
ESEND
Failed to transmit data to the SNTP server. Check the GX/GP Ethernet
cable connection and IP address setting.
ERECV
Failed to receive data from the SNTP server. Check the GX/GP Ethernet
cable connection and IP address setting.
EBROKEN
The SNTP server returned an invalid response. The SNTP server may
in a condition that cannot deliver time information. Check the SNTP
server status.
ETIMEDOUT
The response from the SNTP server timed out. Check the GX/GP
Ethernet cable connection.
EOVER
The time difference between the GX/GP and SNTP server has exceeded
the limit for correcting the time. Check whether the SNTP server is
running properly and the limit for correcting the time.
2.3 Displaying Various Types of Information