4-5

IM 04L51B01-01EN

Using Modbus Functions (Communicating with Modbus devices)

1

2

3

4

5

App

Examples of Setting Commands

The following are command setting examples on the GX/GP when the GX/GP is a Modbus

client device. If the GX/GP is a Modbus master device, substitute “master” for “client” and

“slave” for “server.”

Ethernet

GX/GP

(Modbus client)

Instrument A

(Modbus server 1)

Instrument B

(Modbus server 2)

Instrument C

(Modbus server 3)

Connection example

Loading into Communication Channels

The GX/GP enters data loaded from the server into communication channels as floating

point type data.

Example 1

Load the 16-bit signed integer value assigned to register 30001 of instrument A to C001.

C001

30001

Communication channel data

Register of instrument A

16-bit signed integer

Command setting

Setup Item

Value

Client command number

1

Command setting

Type

Read

Server

1

Data type

INT16

Register

30001

Channel type

Communication channel

First-CH

C001

Last-CH

C001

Example 2

Load the 32-bit signed integer value assigned to registers 30003 and 30004 (little endian) of

instrument B to C003. Only the smallest register number need be specified in commands.

30003

Lower bytes

Higher bytes

30004

C003

32-bit signed integer

Register of instrument B

Communication channel data

Command setting

Setup Item

Value

Client command number

2

Command setting

Type

Read

Server

2

Data type

INT32_L

Register

30003

Channel type

Communication channel

First-CH

C003

Last-CH

C003

4.2 Using Modbus/TCP to Enable the GX/GP to Read Data from and Write Data to Other Devices (Modbus client function)