5 e-mail format, E-mail format -55 – Yokogawa Touch Screen GP20 User Manual

Page 307

Advertising
background image

3-55

IM 04L51B01-01EN

Using Network Functions (Ethernet interface)

1

2

3

4

5

App

3.2.5

E-mail Format

The formats of alarm notification mail, periodic notification mail, power failure notification

mail, memory full notification mail, system error notification mail, report notification mail, and

test mail are given below.

Alarm Notification Mail Format

• Subject

Subject

[Alarm_Summary]sss···s-ttt···t

• Syntax

Header block

headerCRLF

CRLF

General block

Alarm_notificationCRLF

<Host name>CRLF

hostCRLF

CRLF

Alarm information

<CH>

ccc···cCRLF

<Type>

lqCRLF

<aaa>yyyy/mo/dd_hh:mi:ssCRLF
:

CRLF

Instantaneous data

<Inst. value>CRLF

yyyy/mo/dd_hh:mi:ssCRLF

ccc···c=ddd···duuu···uCRLF

CRLF
:

CRLF

Source URL

Access_the_following_URL_in_order_to_look_at_a_screen. CRLF

http://host.domain/CRLF

CRLF

Display item description

ttt···t

Tag number or channel number (when tag or channel is attached to the

header)

ccc···c

Tag number, tag, or channel number

(Channels set to skip or off are not output.)

lq

Alarm level (1 to 4)

Alarm type (H, L, R, r, T, t, h, l)

H (high limit alarm), L (low limit alarm), R (high limit on rate-of-change

alarm), r (low limit on rate-of-change alarm), T (delay high limit alarm),

t (delay low limit alarm), h (difference high limit alarm), l (difference low

limit alarm)

aaa

Alarm status (On, Off)

ddd···d

Measured value, computed value (up to 10 digits including the sign and

decimal point)

+OVER (positive overflow)

–OVER (negative overflow)

Burnout

******* (error data)

The GX/GP transmits channel numbers, alarm types, and alarm statuses for up to 10 events

in a single e-mail. If the GX/GP is configured to include a tag number or a channel number in

the e-mail subject, one e-mail is sent for each event.

3.2 Transmitting E-mail Messages

Advertising