Example 3

Load the 16-bit signed integer values assigned to registers 30001 and 30002 of instrument

B to C001 and C002. Only the smallest register number need be specified in commands.

30001

16-bit signed integer
16-bit signed integer

30002

C001
C002

Register of instrument B

Communication channel data

Command setting

Setup Item

Value

Client command number

3

Command setting

Type

Read

Server

2

Data type

INT16

Register

30001

Channel type

Communication channel

First-CH

C001

Last-CH

C002

Example 4

Load the 32-bit floating point values assigned to registers 30005 and 30006 (little endian) of

instrument B to C004. Only the smallest register number need be specified in commands.

30005

Lower bytes

Higher bytes

30006

C004

32-bit floating point

Register of instrument B

Communication channel data

Command setting

Setup Item

Value

Client command number

4

Command setting

Type

Read

Server

2

Data type

FLOAT_L

Register

30005

Channel type

Communication channel

First-CH

C004

Last-CH

C004

Writing Data to a Server

Example

Write the measured value from channel 0001 to register 40001 of instrument A.

16-bit signed integer

I/O channel

Register of instrument A

0001

40001

Command setting

Setup Item

Value

Client command number

5

Command setting

Type

Write

Server

1

Data type

INT16

Register

40001

Channel type

I/O channel

First-CH

0001

Last-CH

0001

4.2 Using Modbus/TCP to Enable the GX/GP to Read Data from and Write Data to Other Devices (Modbus client function)