● Digital display

Displays measured values numerically

A DI input state can be displayed as an arbitrary

character string (0=Off/1=On, etc.)

Update rate: 0.5 s

● Overview display

Display format: All channels (GX10: Max. 30,

GX20: Max. 100), each groups

Displays the measured values of all channels

and the alarm statuses

● Alarm summary display

Displays a log of up to 1000 alarms

Specify an alarm with the cursor and jump to

the corresponding section on the historical trend

display.

● Message summary display

Time and content of up to 500 messages

(including 50 add messages)

Specify a message with the cursor and jump to

the corresponding section on the historical trend

display.

● Memory summary display

Displays the information (up to 500) of the data

in the memory

Specify a file with the cursor and jump to the

corresponding section on the historical trend

display.

● Report display

Displays the report data residing in the internal

memory

For more details, see "MATHEMATICAL

FUNCTIONS WITH REPORT FUNCTION (/MT)."

● Log display

Displays the event log, error log, communication

log, FTP log, Web log, e-mail log, SNTP log,

DHCP log, and Modbus log.

● Multi-panel display

Divides the screen into two to six sections and

displays some different display formats.

● Other displays

Network information display

System information display

System configuration display

Auto scroll ON/OFF:

The displayed groups can be automatically

switched at a specified interval.

The display switches in ascending group order.

Names of channels:

Channel number;

Analog input: 01 to 10

Digital input: 01 to 16

Digital output: 01 to 06

X X X X

Slot number; GX10: 0 to 2, GX20: 0 to 9
Main unit: 0

Tags:

• Tag and Tag numbers can be displayed.

• Tag number; Number of characters: Up to 16

Displayable characters: Alphanumeric characters

Tag numbers can be enabled or disabled.

• Tag; Number of characters: Up to 32

Displayable characters: Alphanumeric characters

Message:

• Write messages to the trend display.

• Number of messages: 100

• Number of characters: Up to 32

• Write method: Write a preset message or write

an arbitrary message on the spot.

• Write destination: Select only the displayed

group or all groups.

• Auto message: Write a message when the GX

recovers from a power failure while memory

sampling is in progress.

Write a message when the trend interval is

switched during memory sampling.

Add message:

• Write messages to the past data positions.

• Message: The same as the “Message” item

above

Number of writable messages per file: 50

messages (including 10 freehand messages)

Freehand message:

• Can be written by dedicated pen.

Number of writable messages per file: 50

messages (including 10 Add messages)

Data Saving Functions

Internal memory:

• Temporarily saves various types of data.

• Medium: Flash memory

• File storage capacity: 500 MB

External storage medium:

• Medium SD card (SD/SDHC) (up to 32 GB)

• Format: FAT32 or FAT16

Data type:

• Display data, Event data, Alarm summary data,

Manual sampled data, Screen image data, Setup

data, and Report data

Display data:

• Target: Measurement (input/output module)/

math/communication channels, alarm summary,

message summary

Description: Maximum or minimum value per

recording interval

• Recording intervals: Determined by the trend

interval

For GX20

Trend interval (div)

Number of channels

5 s

100

10 s

200

15 s or longer

500

Note that the maximum number of channels is

fixed at 100 in the GX10.

• Data size;

Analog input data: 12 bytes/ch.

Digital I/O data: 4 bytes/ch.

Math channel data: 12 bytes/ch.

Communication channel data: 12 bytes/ch.

• File size: Up to 18 MB

• Number of files: Up to 500 (including event data)

Operation in the internal memory: FIFO (First In

First Out)

• Data format: Binary or text

• Recording: Records data at all times.

• Display data file sample time

Measurement channel = 30. Math Channel = 0