Configuring the GX/GP

1

2

3

4

5

App

Explanation

Operation of Gradually Correcting the Internal Clock

If the time deviation between the time of the GX/GP internal clock and the correct time (the

specified time) is within a specified value, the GX/GP clock is adjusted gradually at a rate

of 1 ms per second. The maximum value of time deviation (tm in the figure below) can be

selected in the range of 5 s to 15 s.

Time specified using keys or

retrieved from an SNTP server

Range in which the time is

gradually adjusted

Nearest

hour

Time deviation

Time when the remote control

signal is applied

(GX/GP time)

tm

tm

Range in which the time is

gradually adjusted

GX/GP

time

Time deviation

tm

tm

Example: When changing the time to 12 hours 55 minutes 35 seconds when the internal

clock is 12 hours 55 minutes 32 seconds

The time deviation of 3 seconds is adjusted 1 ms per second. The internal clock will be

synchronized to the specified time 50 minutes later.

1.18 Configuring System Settings (Time zone, display language, status relay, etc.)