Yokogawa Touch Screen GP20 User Manual

Page 73

Advertising
background image

1-59

IM 04L51B01-01EN

Configuring the GX/GP

1

2

3

4

5

App

Special Computations

PRE( )
(Syntax) PRE(e1)

(Condition) Determines the previous value of e1.
HOLD(a):b
(Syntax) HOLD(a):b

(Condition) When a is zero, b is carried out to derive the computed value. Otherwise, the

previous computed value is held.

Expression Example
Under normal conditions, TLOG.SUM(0001) is carried out to derive the computed value.

When [0001] exceeds K01, the previous computed value is held.

HOLD(0001.GT.K001):TLOG.SUM(0001)

K001

RESET(a):b
(Syntax) RESET(a):b

(Condition) When a is zero, b is carried out to derive the computed value. Otherwise,

the previous computed value of b is reset, and b is carried out to derive the

computed value.

Expression Example
Under normal conditions, TLOG.SUM(0001) is carried out to derive the computed value.

When [A001] exceeds K01, the previous computed value is reset, and TLOG.SUM(0001)

is carried out.

RESET(A001.GT.K001):TLOG.SUM(0001)

K001

Reset

CARRY(a):b
(Syntax) CARRY(a):b

(Condition) Only TLOG.SUM can be specified for b. If the computed value X of b is

less than a, the computed result is X. If X is greater than or equal to a, the

computed result is the excess (X – a).

(Explanation) When a value such as the flow rate is summed and the threshold value is

reached or exceeded, the sum value is reset while carrying over the amount

that exceeded the threshold value.

Expression Example
Expression that sums the values of channel 0001 and resets the value when it reaches or

exceeds 10000.

K001=10000

CARRY(K001):TLOG.SUM(0001)

K001

Examples of Equations That Are Not Allowed
0002+HOLD(K001):TLOS.SUM(0001)

Reason: HOLD is not at the beginning of the expression.
RESET(A001.GT.K001):TLOG.SUM(0001)+RESET(A001.GT.K001):0002

Reason: RESET appears twice in one equation.

1.5 Configuring Math Channels

Advertising