Input/output module specifications, Analog input module (model gx90xa or option /uxx0), Contents>> <<index – Yokogawa Touch Screen GP20 User Manual

Page 435: Gx90xa

Advertising
background image

10

All Rights Reserved. Copyright © 2012-2013, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 04L52B01-01EN

May. 7, 2013-00

INPUT/OUTPUT MODULE SPECIFICATIONS

GX90XA

ANALOG INPUT MODULE (Model GX90XA or Option /Uxx0)

• Number of inputs: 10

• Input Type: DC voltage, standard signal, thermocouple (TC), resistance temperature

detector (RTD)*1, ON/OFF input (DI), and DC current (by adding an external shunt

resistor)

• Measurement interval: 100*1, 200*1, 500 ms*1, 1, 2, 5 s

• Input range: -5% or more and 105% or less (accuracy is guaranteed in the range

from 0% to 100% inclusive)

• Measurement ranges and accuracies

*2

(However, the number of display digits can

be increased by scaling.)

*1 Cannot be specified for the electromagnetic relay scanner type (Type Suffix Code: -T1).

*2 The following specifications apply to operation of the recorder under standard operation

conditions. Temperature: 23 ± 2 °C, Humidity: 55% ± 10% RH, Power supply voltage: 90 to 132

or 180 to 250 VAC, Power supply frequency: 50/60 Hz ± 1%, Warm-up time: At least 30 min.

Other ambient conditions such as vibration should not adversely affect recorder operation.

Input Type

Range

Measurement accuracy (digital display)

Max. resolution

of digital display

A/D integration time: 16.7ms or more

A/D integration time: 1.67ms

DCV

20 mV

-20.000

to

20.000 mV

±(0.05 % of rdg + 12 μV)

±(0.1 % of rdg + 40 μV)

1 μV

60 mV

-60.00

to

60.00 mV

±(0.05 % of rdg + 0.03 mV)

±(0.1 % of rdg + 0.15 mV)

10 μV

200 mV

-200.00

to

200.00 mV

±(0.05 % of rdg + 0.03 mV)

±(0.1 % of rdg + 0.4 mV)

10 μV

1 V

-1.0000

to

1.0000 V

±(0.05 % of rdg + 1.2 mV)

±(0.1 % of rdg + 4 mV)

100 μV

2 V

-2.0000

to

2.0000 V

±(0.05 % of rdg + 1.2 mV)

±(0.1 % of rdg + 4 mV)

100 μV

6 V

-6.000

to

6.000 V

±(0.05 % of rdg + 3 mV)

±(0.1 % of rdg + 15 mV)

1 mV

20 V

-20.000

to

20.000 V

±(0.05 % of rdg + 3 mV)

±(0.1 % of rdg + 40 mV)

1 mV

50 V

-50.00

to

50.00 V

±(0.05 % of rdg + 0.03 V)

±(0.1 % of rdg + 0.15 V)

10 mV

Standard

signal

0.4-2V

0.3200

to

2.0800 V

±(0.05 % of rdg + 1.2 mV)

±(0.1 % of rdg + 4 mV)

100 μV

1-5V

0.800

to

5.200 V

±(0.05 % of rdg + 3 mV)

±(0.1 % of rdg + 15 mV)

1 mV

TC

(Excluding

RJC

accuracy)

R

0.0

to

1760.0 °C

±(0.15 % of rdg + 1.0 °C)

However, R, S; 0.0 to 800.0 °C: ±2.2 °C,

B; 400.0 to 800.0 °C: ±3.0 °C

Accuracy at less than 400.0 °C is not guaranteed.

±(0.2 % of rdg + 6.0 °C)

However, R, S; 0.0 to 800.0 °C: ±7.6 °C,

B; 400.0 to 800.0 °C: ±11.0 °C

Accuracy at less than 400.0 °C is not guaranteed.

0.1 °C

S

0.0

to

1760.0 °C

B

0.0

to

1820.0 °C

K

-270.0

to

1370.0 °C

±(0.15 % of rdg + 0.7 °C)

However, -200.0 to 0.0 °C: ±(0.35 % of rdg + 0.7 °C)

Accuracy at less than -200.0 °C is not guaranteed

±(0.2 % of rdg + 5.0 °C)

However, -200.0 to 0.0 °C: ±(3 % of rdg + 5.0 °C)

Accuracy at less than -200.0 °C is not guaranteed

0.1 °C

-200.0

to

500.0 °C

E

-270.0

to

800.0 °C

±(0.15 % of rdg + 0.5 °C)

However, -200.0 to 0.0 °C: ±(0.35 % of rdg + 0.5 °C)

Accuracy at less than -200.0 °C is not guaranteed

±(0.2 % of rdg + 4.0 °C)

However, -200.0 to 0.0 °C: ±(2 % of rdg + 4.0 °C)

Accuracy at less than -200.0 °C is not guaranteed

0.1 °C

J

-200.0

to

1100.0 °C

T

-270.0

to

400.0 °C

±(0.15 % of rdg + 0.5 °C)

However, -200.0 to 0.0 °C: ±(0.35 % of rdg + 0.5 °C)

Accuracy at less than -200.0 °C is not guaranteed

±(0.2 % of rdg + 2.5 °C)

However, -200.0 to 0.0 °C: ±(2 % of rdg + 2.5 °C)

Accuracy at less than -200.0 °C is not guaranteed

0.1 °C

N

-270.0

to

1300.0 °C

±(0.15 % of rdg + 0.7 °C)

However, -200.0 to 0.0 °C: ±(0.7 % of rdg + 0.7 °C)

Accuracy at less than -200.0 °C is not guaranteed

±(0.3 % of rdg + 6.0 °C)

However, -200.0 to 0.0 °C: ±(5 % of rdg + 6.0 °C)

Accuracy at less than -200.0 °C is not guaranteed

0.1 °C

W

0.0

to

2315.0 °C

±(0.15 % of rdg + 1.5 °C)

±(0.3 % of rdg + 14.0 °C)

However, more than 1000.0 °C: ±(0.8 % of rdg

+ 9.0 °C)

0.1 °C

L

-200.0

to

900.0 °C

±(0.15 % of rdg + 0.5 °C)

Less than 0.0 °C: ±(0.5 % of rdg + 0.5 °C)

±(0.2 % of rdg + 4.0 °C)

Less than 0.0 °C: ±(3 % of rdg + 4.0 °C)

0.1 °C

U

-200.0

to

400.0 °C

±(0.15 % of rdg + 0.5 °C)

Less than 0.0 °C: ±(0.7 % of rdg + 0.5 °C)

±(0.2 % of rdg + 2.5 °C)

Less than 0.0 °C: ±(3 % of rdg + 2.5 °C)

0.1 °C

W97Re3-

W75Re25

0.0

to

2320.0 °C

±(0.2 % of rdg + 2.5 °C)

±18.0 °C

More than 2000.0 °C: ±0.9 % of rdg

0.1 °C

KpvsAu7Fe

0.0

to

300.0 K

±(0.15 % of rdg + 2.0 K)

0.15 to 280.15K: guaranteed range

±(0.2 % of rdg + 7.0 K)

0.15 to 280.15K: guaranteed range

0.1 K

Platinel 2

0.0

to

1395.0 °C

±(0.25 % of rdg + 2.3 °C)

±(0.25% of rdg + 8.0 °C)

0.1 °C

PR20-40

0.0

to

1900.0 °C

±(0.7 % of rdg + 0.4 °C)

However, accuracy at less than 800.0 °C is not

guaranteed.

±20.0 °C

However, accuracy at less than 800.0 °C is not

guaranteed.

0.1 °C

NiNiMo

0.0

to

1310.0 °C

±(0.25 % of rdg + 0.7 °C)

±(0.5% of rdg + 5.0 °C)

0.1 °C

W/

WRe26

0.0

to

2320.0 °C

±(0.2 % of rdg + 2.0 °C)

However, accuracy at less than 300.0 °C is not

guaranteed.

±(0.4 % of rdg + 12.0 °C)

However, accuracy at less than 300.0 °C is not

guaranteed.

0.1 °C

N(AWG14)

0.0

to

1300.0 °C

±(0.2 % of rdg + 1.3 °C)

±(0.5% of rdg + 7.0 °C)

0.1 °C

XK GOST

-200.0

to

600.0 °C

±(0.25 % of rdg + 0.8 °C)

±(0.5% of rdg + 4.0 °C)

0.1 °C

Advertising
This manual is related to the following products: