Status Output

The status below is output with a relay contact signal. You can select whether each status is

output to the relay. The relay is energized when the status occurs.

You cannot change this behavior.

Status

Description

Corrective Action

Internal memory

or SD card status

Error in the internal memory.

Contact your nearest YOKOGAWA dealer

for repairs.

When the auto save function to the SD memory card is On

• The free space on the SD memory card

dropped to 10% of the total size (only

when the media FIFO ( see page 1-91 in

section 1.9.2, “Setting the Save Method

to Media (Auto save or manual save) and

Media FIFO”) is disabled).

Replace the SD memroy card.

The status of the internal memory is

output when the SD memory card is not

inserted or error in the SD memory card.

• The available space in the internal

memory dropped to 25 MB or less.

1

• The number of files in the internal

memory for which Auto Save to the SD

memory card has not been completed

has exceeded 490.

Insert an SD memory card.

When the auto save function to the SD memory card is Off

• The available space in the internal

memory dropped to 25 MB or less.

1

• The number of files in internal memory

for which Manual Save has not been

completed has exceeded 490.

Save the data in the internal memory to

the SD memory card.

Measurement

error

Error in the A/D converter.

Contact your nearest YOKOGAWA dealer

for repairs.

Burnout has been detected. A burnout

can occur when thermocouple or RTD

wires are disconnected or when unified

signals are outside the specifications.

Check the cause of the burnout.

Module error has been detected.

On the system information screen,

check whether the module is connected

correctly and whether it is being

recognized properly.

Communication

error

A Modbus master or Modbus client

communication error has occurred.

Check the error in the Modbus master or

Modbus client screen and carry out the

corrective action.

Record stop

Recording has stopped.

Start recording.

Alarm occurrence An alarm has occurred.

Check the alarm.

1 The internal memory’s “available space” refers to the following quantities.

• Unused areas

• Areas of data for which Auto Save or Manual Save ( see page 1-91 in section 1.9.2, “Setting the

Save Method to Media (Auto save or manual save) and Media FIFO”) has been completed.

Relay Operation

NO

C

NC

During normal operation

NO

C

NC

When the specified status occurs

NO

C

NC

When power is turned off

1.18 Configuring System Settings (Time zone, display language, status relay, etc.)