4-23

IM 04L51B01-01EN

Using Modbus Functions (Communicating with Modbus devices)

1

2

3

4

5

App

I/O Channel Data

Input Register

Data Type

• There is no decimal place information.

Error code

Meaning

0

No error

1

Skip

2

+Over

3

–Over

4

+Burnout

5

–Burnout

6

A/D error

7

Invalid data

16

Computation error

17

Communication error

5 bits

4 bits

Status information

Alarm list

0

Reserved

area

Error code

RJC error

A/D calibration

value error

0 0 0 0

Level 1

Level 2

Level 3

Level 4

2 bytes

Higher Lower

GX/GP Status

Data

Register

Description

Data Type

Measuring

308001

0: Recording stopped

1: Recording

16-bit signed integer

Computing

308002

0: Computing stopped

1: Computing

Alarm activated

308003

0: No alarm

1: Alarm occurrence

E-mail started

308004

0: No e-mail transmission

1: E-mail transmission

available

Memory end

308005

0: Space available in the

internal memory or external

storage

1: Not much space in the

internal memory or external

storage

Screen login status

308006

0: No login

1: Logged in

Modbus communication

error

308007

0: Modbus master or client

command normal

1: Modbus master or client

command error

4.5 Modbus Function and Register Assignments