Operating the GX/GP

1

2

3

4

5

App

Modbus Log

Scroll

Communication type (C: client, M: master)

Date and time

Communication status

Recipient/error

Drag or flick

to scroll

Flag

Description

C

Communication by the Modbus client function (Ethernet)

M

Communication by the Modbus master function (serial)

Status

Factor

Description

W

Write

R

Read

Blue

Normal communication.

Yellow

An external Modbus device returned an error response.

Orange

TCP connection in progress.

Red

Failed to connect to an external Modbus device.

Common

to colors

other than

blue

Skip

Command not set.

INVALID

Command cannot be executed.

WAITING

Communication with an external device is congested. Waiting for

recovery. Check the connection with the external device.

CLOSED

Modbus communication was stopped, and connection to the external

device was closed.

RESOLVING

Server/slave connection being established (resolving address).

CONNNECTING

Server/slave connection being established (requesting connection).

UNREACH

The external device was not found on the network. Check the Modbus

server address setting and Ethernet cable connection.

TIMEOUT

The response from the external device timed out. Check the

connection with the external device.

BROKEN

A CRC error was detected in the serial communication with the external

device. Check the serial communication baud rate and other settings.

ERR_FC

The external device returned an error response. Check whether the

Modbus registers are set correctly to match the external device.

ERR_ADDR

ERR_VALUE

ERR_DEVICE

ERR_ACK

ERR_BUSY

ERR_NEGATIVE

ERR_GATE_PATH

ERR_GATE_

TARGET

BAD_SLAVE

The external device returned an invalid response. Check whether the

external device is operating properly.

BAD_FC

BAD_ADDR

BAD_NUM

BAD_CNT

VALID

Modbus communication was established normally.

START

Modbus communication started.

STOP

Modbus communication stopped.

DROPOUT

Failed to send all commands within the specified communication

interval. Check the number of Modbus commands and the baud rate.

2.3 Displaying Various Types of Information