Explanation

TLOG Computation

TLOG computation determines the sum, maximum, minimum, average, or the difference

between the maximum and minimum of a specific channel for each interval determined by a

timer.

Computation Data Dropout

A computation data dropout occurs if the computation is not completed within the scan

interval.

• The math icon in the status display section turns yellow.

• When a computation data dropout occurs, the computed data of the scan interval in which

the dropout occurred is set to the data immediately before the dropout.

• If computation data dropout occurs frequently, reduce the load on the CPU by reducing

the number of math channels or setting a longer scan interval.

Numeric Display and Recording

The range of displayed values of computed data is from –9999999 to 99999999 excluding

the decimal point. The decimal place corresponds to the decimal place of the lower limit

span of the math channel. On the numeric display, values are displayed if the computed

result is within the above range regardless of the upper and lower limits of span.

The following table indicates special displays.

Display/Recording

Computed Data Status

+Over

• +Display over: When a computed result exceeds 99999999

• +Computation over: When a value exceeds approximately 1.79E+308 in

the middle of the computation

• When a computation error

1

occurs (you can select +Over or –Over.)

–Over

• –Display over: When a computed result is less than –9999999

• –Computation over: When a value is less than approximately

–1.79E+308 in the middle of the computation

• When a computation error

1

occurs (you can select +Over or –Over.)

1 Computation error occurs when the following computation is carried out.

• /0, SQR(–X), or LOG(–X)

• If a channel number set to skip or Off is used in the equation

Special Data Processing

This section explains the handling of special data in TLOG computation, CLOG computation,

and reports.
Power Failure Operation (TLOG and Reports)
If a power failure occurs when the report function is enabled or in the middle of the TLOG

computation, the report operation and TLOG computation resume when the GX/GP recovers

from the power failure. The operation varies depending on whether the GX/GP recovers from

the power failure before or after the time to create a report or the TLOG interval timeout.

Time of Recovery

Operation

After the time to create

the data

The report data is created immediately after the GX/GP recovers. The

measured data up to when the power failure occurred is used to create

the report. When the time to create the next report data arrives, the data

after the recovery is used. The interval timer for TLOG data expires

immediately after the GX/GP recovers.

Before the time to create

the data

After the GX/GP recovers, report data is created at the normal time to

create the data.

The measured data excluding the power failure period is used to create

the report.

The interval timer for TLOG data expires after the GX/GP recovers.

Error Data Handling (TLOG, CLOG, and Reports)

If an error occurs in the channel data, the error data is discarded, and the computation

continues. If all the data are in error, an error results.

The following types of data are considered error data.

• Channels set to skip or Off.

• The measured result on an I/O channel is error (A/D converter failure, etc.).

• I/O channel input is in a burnout condition.

• The computed result on a math channel is error.

1.5 Configuring Math Channels