Handling of Overflow Data

1

1 Refers to over range on an I/O channel, computation overflow on a math channel, and over

range on a communication channel.

For TLOG, CLOG, and Reports
When the channel data is overflow data, the GX/GP handles it as follows:

Computation Type

Description

Average value or sum value Set the handling to Error, Skip, or Limit.

Error: Sets the computation result to computation error.

Skip: Discards overflow data and continues the computation.

Limit: Replaces overflow data with the limit value and continues the

computation.

Limit value: Span upper or lower limit or the scale upper or lower limit of

the channel

Maximum, minimum,

Maximum – minimum

Set the handling to Over or Skip.

Over: Computes by using the overflow data.

Skip: Discards overflow data and continues the computation.

For Multiplication and Relation Computation EQ and NE

Computation Type

Computation

Computed Result

Multiplication

0*(+Over)

0

0*(–Over)

0

(+Over)*0

0

(–Over)*0

0

.EQ.

(+Over).EQ.(+Over)

0

(–Over).EQ.(–Over)

0

.NE.

(+Over).NE.(+Over)

1

(–Over).NE.(–Over)

1