• Noise reduction ratio

Integration time

*1

Normal mode

Common mode

1.67 ms

50/60 Hz, no noise

reduction

More than 80 dB

*2

*4

More than 16.7 ms

More than 40 dB

*2

*3

More than 120 dB

*2

*4

*1 A frequency discrimination setting is made in the

main unit.

*2 A resistance temperature detector range is a

converted value of voltage when a measured

current flows.

*3 50/60 Hz ± 0.1 %

*4 50/60 Hz ± 0.1%, 500 Ω imbalance, between

minus measuring terminal and ground

• Normal mode voltage for TC/ DC voltage (1 V

range or less)/DI: 1.2 times or less of rated range

Standard signal 0.4 to 2 V range: 2.4 V

Standard signal 1-5 V range: 6 V

RTD (100 Ω): 50 mV peak

RTD (50 Ω): 50 mV peak

* 50/60Hz, The peak value including the signal.

• Maximum common mode voltage for measuring

input: 30 V ACrms (50/60Hz) or 60 V DC

(However, maximum common mode noise

voltage for measuring input: 250 V ACrms)

• Maximum voltage between measuring input

channels: 30 V ACrms (50/60 Hz) or 60 V DC

(maximum common mode noise voltage for

measuring input: 250 V ACrms)

• Reference junction compensation accuracy:

When measuring temperature greater than

or equal to 0 °C and when input terminal

temperature is balanced

Type K, E, J, T, N, XK GOST: ±0.5 °C (23 °C ± 2

°C), ±0.7 °C (0 to 50 °C), ±1.0 °C (-20 to 60 °C)

Type R, S, W, L, U, W97Re3-W75Re25,

Platinel2, NiNiMo, W/WRe26, N(AWG14): ±1.0

°C (23 °C ± 2 °C), ±1.4 °C (0 to 50 °C), ±2.0 °C

(-20 to 60 °C)

Type KpvsAu7Fe: ±1.0 K (23 °C ±2 °C), ±1.4 K

(0 to 50 °C), ±2.0 K (-20 to 60 °C)

Type B, PR20-40: Internal reference

compensation is fixed to 0°C

• Sampling interval/A/D integration time:

10 ch. mode

Solid state relay scanner type*1

Sampling interval

Integration time

100 ms/200 ms

1.67 ms

500 ms or more

16.7 ms/20 ms

1 s or more

36.7 ms

2 s or more

100 ms

Electromagnetic relay scanner type

Sampling interval

Integration time

1 s or more

16.7 ms/20 ms

2 s or more

36.7 ms

5 s

100 ms

2 ch. mode*2

Sampling interval

Integration time

100 ms or more

16.7 ms/20 ms

1 s or more

36.7 ms

2 s or more

100 ms

*1 In 10ch mode, when the scan interval is set to 100

ms or 200 ms, the A/D integration time is fixed at

1.67 ms. This prevents power frequency noise

from being eliminated, causing measured values

to wobble.

*2 Cannot be specified for the electromagnetic relay

scanner type (Type Suffix Code: -T1).

• Calibration correction:

Mode: Linearizer Approximation, Linearizer Bias

Number of set points: 12

• Terminal type*: M3 screw terminal or Clamp terminal

* M3 screw terminals only for the electromagnetic

relay scanner type.

• Withstand voltage

Between the input circuits and the internal circuit:

3000 V AC for one minute

Between the analog input channels: 1000 V AC

for one minute (excluding b-terminal)

• Insulation resistance:

Between the input terminal and the internal

circuit: 20 MΩ or greater at 500 VDC

• Recommended replacement period of

electromagnetic relay scanner type modules:

Electromagnetic relay scanner type modules

make measurements by switching mechanical

contact relays on and off.

To ensure that the modules continue to operate

reliably and correctly, replace them

Continuous use at measurement interval 1 s: 1 year

Continuous use at measurement interval 2 s: 2 years

Continuous use at measurement interval 5 s: 5 years

Safety and EMC Standards

• CSA: CSA22.2 No.61010-1, installation category

II (*1), pollution degree 2 (*2), and CSA-C22.2

NO. 61010-2-030-12

• UL: UL61010-1, UL 61010-2-030 (CSA NRTL/C)

• CE:

EMC directive

EN61326-1 compliance, Class A Table 2

EN61000-3-2 compliance

EN61000-3-3 compliance

EN55011 Class A Group 1

Low voltage directive

EN61010-1, EN 61010-2-030

Installation category II (*1)

Pollution degree 2 (*2)

Measurement category II (*3)

• Maximum input voltage for measuring input: ± 60 V DC

• Maximum common mode noise voltage for

measuring input: 30 V ACrms 50/60 Hz or 60 V

DC (However, maximum common mode noise

voltage for measuring input: 250 V AC)

• C-Tick: EN55011 compliance, Class A Group 1

• KC marking: Electromagnetic wave interference

prevention standard, electromagnetic wave

protection standard compliance

*1 Installation category (overvoltage category) II:

Describes a number which defines a transient

overvoltage condition.