1.6 Setting Display Conditions

Set the display conditions.

1.6.1

Setting the Trend Interval

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu Display settings > Trend

interval

Web browser:

Config. tab > Display settings > Trend interval

Hardware configurator:

Display settings > Trend interval

Description

Setup Item

Selectable Range or Options

Default Value

Trend interval [/div]

1

5s

2

, 10s

2

, 15s

2

, 30s, 1min, 2min, 5min, 10min,

15min, 20min, 30min, 1h, 2h, 4h, 10h

1min

Trend rate switching

Off, On

Off

Second interval [/div]

1

5s

2

, 10s

2

, 15s

2

, 30s, 1min, 2min, 5min, 10min,

15min, 20min, 30min, 1h, 2h, 4h, 10h

1min

1 Does not appear if the recording mode is set to

Event in basic settings under recording settings

Appears when trend rate switching is set to

On.

2 Cannot be specified if an electromagnetic relay scanner type (Type suffix code: -T1) analog

input module is in use (configure).

Trend interval [/div]

Set the trend interval.

Relationship between the Scan Interval and Trend Interval
The shortest trend interval that you can specify varies depending on the scan interval.

Scan Interval

Shortest Trend Interval

100 ms

5 s

200 ms

10 s

500 ms

15 s

1 s

30 s

2 s

1 min

5 s

5 min

Trend rate switching

Set this to

On to enable the function that switches the trend interval while the recording is in

progress.

During data acquisition, you can switch from the normal trend interval to the secondary trend

interval. You can also switch back to the normal trend interval.

Note

Only the displayed time axis changes when you switch to the secondary trend interval. The trend

interval of recording data does not change.

Second interval [/div]

Set the time per division for the secondary interval. You cannot choose a secondary interval

that is shorter than the scan interval.