Scale, Low-cut – Yokogawa Touch Screen GP20 User Manual

Page 28

Advertising
background image

1-14

IM 04L51B01-01EN

Scale

1

Setup Item

Selectable Range or Options

Default Value

Decimal Place

0, 1, 2, 3, 4, 5

2

Scale Lower

–999999 to 999999

0.00

Scale Upper

–999999 to 999999

100.00

Unit

Character string (up to 6 characters,

A a # 1

) —

1 Appears when math is set to

Linear scaling or Square root.

Decimal Place

Set the decimal place of the scale for linear scaling and square rooting.

Span Lower, Scale Upper

Assign values to the results of unit conversion of linear scaling and square rooting.

Note

• The GX/GP converts measured values to values within the range set by the

Scale Lower

and

Scale Upper values with their decimal points removed. For example, if the scale setting

is “–5 to 5,” values are converted to values within the span of “10”; if the scale setting is “–5.0

to 5.0,” values are converted to values within a span of “100.” In this case, the resolution of

values converted to a span of “10” is lower than those converted to a span of “100.” To prevent

the display from becoming coarse, it is recommended that the scale be set so that the span is

greater than 100.

• You cannot set the same value to

Scale Lower and Scale Upper.

Unit

Set the unit.

Low-cut

1

Setup Item

Selectable Range or Options

Default Value

On/Off

Off, On

Off

Low-cut value

2

0.0% to 5.0%

0.0

Low-cut output

3

Output 0%, Output linear

Output 0%

1 Appears when the type is set to

Volt and Calculation is set to Square root or when the type is

set to

GS and Calculation is set to Linear scaling or Square root.

2 Appears when On/Off is set to

On.

3 Does not appear when the type is set to

GS and Calculation is set to Linear scaling.

On/Off

Select

On to use the low-cut function.

Low-cut value

Set the low-cut value in the range of 0.0% to 5.0% of the input span.

Input value

Measured value

Result of square root computation

Low-cut value

Low-cut output

Set the output value when the input is less than the low-cut value for when the low-cut

function is in use.

Options

Description

Output 0%

Set the value for 0%.

Output linear

Outputs values that result by applying linear scaling to the input on the basis of

the specified span and scale.

Note

When the type is set to

GS and Calculation is set to Linear scaling, the low-cut output is fixed to

Output 0%.

1.2 Configuring AI Channels (Analog input (including DI) channels)

Advertising
This manual is related to the following products: