Burnout set
1
Setup Item
Selectable Range or Options
Default Value
Mode
Off, Up, Down
Off
1 Appears when the range type is set to
GS, TC, or RTD.
Mode
When the range type is set to
GS, TC, or RTD, the GX/GP detects sensor burnouts.
Options
Description
Off
Does not detect burnouts in the sensor.
Up
When the sensor burns out, the measured result is set to +over range. The measured
value is displayed as “Burnout.”
When the range type is set to
GS, the GX/GP assumes that the sensor has burned
out when the measured value falls outside –10 to 110% of the specified span width.
(Example: When the measured value is less than –10 or greater than 110 when the scale
is set to 0 to 100 in linear scaling)
Down
When the sensor burns out, the measured result is set to –over range. The measured
value is displayed as “Burnout.”
When the range type is set to
GS, the GX/GP assumes that the sensor has burned
out when the measured value falls outside –10 to 110% of the specified span width.
(Example: When the measured value is less than –10 or greater than 110 when the scale
is set to 0 to 100 in linear scaling)
Thermocouple Examples
Burnout
Burnout
1 - 5 V
Detected on the 1-5 V value
Indicated as Burnout
Indicated as Burnout
Thermoelectromotive force
Bias
Setup Item
Selectable Range or Options
Default Value
Value
Numeric value (–999999 to 999999)
0
Value
Set the bias to add to input values or linear scaling values (input calculation).
Input value
Measured value
Bias (a constant value)
+
Channel on which bias is added
1.2 Configuring AI Channels (Analog input (including DI) channels)