SPECIFICATIONS OF OPTIONAL

FUNCTIONS

SERIAL COMMUNICATION INTERFACE (/C2, /C3)

• Connection: EIA RS-232(/C2) or EIA RS-

422/485(/C3)

• Protocol: Dedicated protocol or Modbus protocol

• Setting/measurement server function: Operation,

setting or output of measurement data are

available by dedicated protocol.

• Synchronization: Start-stop synchronization

• Transmission mode (RS-422/485):

RS-422: Four-wire half-duplex multi-drop

connection (1:n (n = 1 to 31))

RS485: Two-wire half-duplex multi-drop

connection (1:n (n = 1 to 31))

• Baud rate: 1200, 2400, 4800, 9600, 19200,

38400, 57600, or 115200 bps

• Data length 7 or 8 bits

• Start bit: 1 bit

• Stop bit: 1 bit or 2 bit

• Parity: ODD, EVEN, or NONE

• Handshaking Off: Off, XON: XON, XON: RS, and

CS: RS

• Communication distance; RS-422/485: 1200 m,

RS-232: 15 m

• Modbus/RTU communication: Reading or writing

of measurement data on other instruments is

available by Modbus protocol.

Math channel option is needed to read

measurement data from other instruments.

• Operation modes: Master or slave

VGA VIDEO OUTPUT (/D5) (Only for GX20)

• External display:

Resolution: 800 × 600 dots (VGA)

Connector: 15-pin D-Sub

FAIL OUTPUT (/FL)

• Contact: C contact, 1 point

• FAIL output:

The relay contact output on the rear panel

indicates the occurrence of CPU failure.

Relay operation: Energized during normal

operation and de-energized on CPU failure.

• Rated power supply voltage: 24 V DC or 250 V

AC or less

• Rated load current: 3A (DC)/3A (AC), resistance

load

• Min. load current: 100 mA

• Recommended replacement periods of contact:

Electrical: 30,000 more ON-OFF operations,

Mechanical: 5,000,000 more ON-OFF operations

MATHEMATICAL FUNCTIONS WITH REPORT

FUNCTION (/MT)

Mathematical Function:

• Number of math channels; GX10: 50, GX20: 100

• Operation:

General arithmetic operations: Four arithmetic

operations (+, -, *, /), square root, absolute,

common logarithm, natural logarithm,

exponential, and power

Relational operations: <, ≤, >, ≥, =, and ≠

Logic operations: AND, OR, NOT, and XOR

Statistical operations: TLOG or CLOG

Special operations: PRE, HOLD, RESET, and

CARRY

Conditional operation: [a?b:c]

• Computation accuracy: Double-precision floating

point

• Data that can be used;

Channel data: Measurement channels

(GX10: 0001 to 0216, GX20: 0001 to 0916),

mathematical channels (GX10: A001 to A050,

GX20: A001 to A100), Communication channels

(GX10: C001 to C050, GX20: C001 to C300),

Constants:100 (K001 to K100), Internal switch:

100 (S001 to S100), Flag: 20 (F01 to F20)

Report function:

• Number of report channels; GX10: 50, GX20: 60

• Report types: Hourly + daily, daily + weekly, daily

+ monthly, Batch, Day custom

• Computation types: Average, maximum,

minimum, sum, or instantaneous value

• Unit of sum: OFF, /s, /min, /hour, /day

• Report templates: Office Open XML spreadsheet

files (which can be displayed with Microsoft

Office Excel) or PDF files can be output or

printed out with any LAN-connected printer

supporting the HP-PCL5 language.

COMMUNICATION CHANNEL FUNCTIONS (/MC)

• Number of communication channels; GX10: 50

(C001 to C050), GX20: 300 (C001 to C300)

* Required to record data from Modbus devices or

PCs on the GX/GP.