Hold register, Coil, Input relay – Yokogawa Touch Screen GP20 User Manual

Page 334

Advertising
background image

4-14

IM 04L51B01-01EN

Hold Register

Type

GX/GP Register

Number

Data Type

I/O channel

I/O data

400001 to 401000

32-bit signed integer

401001 to 402000

32-bit floating point

402001 to 402500

16-bit signed integer

Status information

402501 to 403000

16-bit signed integer

I/O channel

(continuous area)

I/O data

404001 to 404200

32-bit signed integer

404201 to 404400

32-bit floating point

404401 to 404500

16-bit signed integer

Status information

404501 to 404600

16-bit signed integer

Communication

channel

Communication data

405001 to 405600

32-bit signed integer

406001 to 406600

32-bit floating point

407001 to 407300

16-bit signed integer

Status information

407501 to 407800

16-bit signed integer

Internal switch

408001 to 408100

16-bit signed integer

GX/GP operation setting

409001 to 410000

16-bit signed integer

Client/Master device

Read

Write

Coil

Type

GX/GP Register

Number

Data Type

I/O channel

I/O data

1 to 500

Bit string

Status information

501 to 1000

Communication

channel

Communication data

1001 to 1300

Status information

1501 to 1800

Internal switch

2001 to 2100

Client/Mastre device

Read

Write

Input Relay

Type

GX/GP Register

Number

Data Type

I/O channel

I/O data

10001 to 10500

Bit string

Status information

10501 to 11000

Math channel

Math data

11001 to 11100

Status information

11501 to 11600

Client/Master device

Read

4.5 Modbus Function and Register Assignments