Saving interval

Set the size of recording data per file. Recording data is divided at the specified file size.

The options vary depending on the number of channels to record and the

Saving interval

setting.

Time

File

File

File

Adding data

A file is also created in the following instances.

• When a file is created manually

• When recording is stopped

• When file creation is executed with the event action function

• After recovering from a power failure
Trend Interval and Display Data Recording Interval

Trend Interval

1

5 s

10 s

15 s

30 s

1min

Recording Interval

100 ms

200 ms

500 ms

1 s

2 s

Selectable range of

file save interval

10 min to

12 hours

10 min to

1 days

10 min to

3 days

10 min to

7 days

10 min to

14 days

Trend Interval

1

2 min

5 min

10 min

15 min

20 min

Recording Interval

4 s

10 s

20 s

30 s

40 s

Selectable range of

file save interval

10 min to

14 days

10 min to

31 days

10 min to

31 days

10 min to

31 days

1 hour to

31 days

Trend Interval

1

30 min

1 h

2 h

4 h

10 h

Recording Interval

1 min

2 min

4 min

8 min

20 min

Selectable range of

file save interval

1 hour to

31 days

1 hour to

31 days

2 hour to

31 days

4 hour to

31 days

8 hour to

31 days

1 You cannot choose a recording interval that is shorter than the scan interval.

Event data

1

Setup Item

Selectable Range or Options

Default Value

Recording Interval

100ms

*4

, 200ms

*4

, 500ms

*4

, 1s, 2s, 5s, 10s, 15s, 20s,

30s, 1min, 2min, 5min, 10min, 15min, 20min, 30min

1s

*5

Recording mode

Free, Single, Repeat

Free

Data length

10min, 20min, 30min, 1h, 2, h, 3h, 4h, 6h, 8h, 12h,

1day, 2day, 3day, 5day, 7day, 14day, 31day

2

Pre-trigger

3

0%, 5%, 25%, 50%, 75%, 95%, 100%

0%

Trigger source operation

3

Off, On

On

1 Appears when the file type is set to

Display + Event or Event.

2 The minimum effective data length based on the recording interval of event data and the

number of recording channels.

3 Appears when the recording mode is not set to

Free.

4 Cannot be specified if an electromagnetic relay scanner type (type suffix code: -T1) analog input

module is in use (configure).

5 2 s if an electromagnetic relay scanner type analog input module is in use.

Recording Interval

Set the event data recording interval. You cannot choose a recording interval that is shorter

than the scan interval.

Note

• The maximum number of channels that the GX20/GP20 can record varies depending on the

recording interval.

Recording Interval

Number of Channels That Can Be Recorded on the GX20/GP20

100 ms

100

200 ms

200

500 ms or more

500

• The GX10/GP10 can record up to 100 channels regardless of the recording interval.