Appendix 5 Power Recovery Operation

This section explains how the GX/GP operates when it recovers from a power failure.

Power Failure Detection

The GX/GP power shuts down when the power is disrupted for the times indicated below.

• 100 to 240 VAC: 1 cycle or more

• 24 VDC/AC: 1 ms or more

Basic Operation

The following operations are retained when the GX/GP recovers from a power failure.

Recording Operation

• If a power failure occurs while the GX/GP is recording, it will continue recording when it

recovers.

• Display and event data files are separated when a power failure occurs.

Monitor Display

• The monitor display is retained.

• If a power failure occurs when a menu is showing, all unsaved settings are discarded,

and the monitor display returns.

• Except for the following cases, trend waveforms continue from the end of waveforms

before the power failure.

• When the file type is set to event data only

• When the trend interval switching function is on

Moving Average

Moving average of AI channels are not retained. When the GX/GP recovers, a new moving

average will start.

Timer Action

• Relative timer

Time action is retained. Relative timers do not count the power failure time.

• Absolute timer, match time timer

If timers expire during a power failure, timeout processing occurs when the GX/GP

recovers.

Remote

Remote conditions are retained. If remote conditions change during a power failure, the

corresponding remote actions are executed when the GX/GP recovers.

Computation

• If a power failure occurs while the GX/GP is computing, it will continue computing when it

recovers.

• Computation results are retained during a power failure.

• Rolling average values are also retained during a power failure.

• If absolute timers or match time timers expire during a power failure, TLOG computation

is performed when the GX/GP recovers.

Report Operation

• If a power failure occurs while the GX/GP is creating a report, it will continue to create it

when it recovers.

• If timers expire during a power failure, timeout processing occurs using the data up to

the power failure when the GX/GP recovers. If this occurs, the report data will contain a

power failure mark.