1-44

IM 04L51B01-01EN

Reset

Alarm ACK

Alarm output relay

Alarm 2

Alarm 1

Relay is activated on the next alarm occurrence.

Activated

Deactivated

Occurrence

Occurrence

Relay deactivated interval

Set the relay’s not-active interval for reflash operation.

Explanation

AND/OR Operation

When multiple alarms are assigned to one alarm output relay, you can select which condition

below will activate the output relay. You can also specify AND operation for internal switches.

• AND: Activated when all assigned alarms are occurring simultaneously

• OR: Activated when any of the specified alarms is occurring

Reflash

When multiple alarms are assigned to one alarm output relay, this function notifies the

occurrence of subsequent alarms after the relay is activated by the first alarm. When

subsequent alarms occur, the output relay is released temporarily. The duration for which the

relays are deactivated can be set to 500 ms, 1 s, or 2 s.

Relays set to Reflash will operate using

Or and Nonhold settings.

Energize or De-energize Operation

You can select whether the alarm output relay is energized or de-energized when an alarm

occurs. If you select de-energize, the alarm output relays will be in the same state when the

GX/GP is shut down as they are when an alarm occurs.

Nonhold/Hold

The alarm output relay can be set to operate in the following fashion when the alarm

condition is no longer met.

• Turn OFF the relay output (nonhold).

• Hold the relay at ON until the alarm ACK is executed (hold).

Alarm ACK Operation

The alarm acknowledge (alarm ACK) operation releases all alarm indications and relay

outputs. For the behavior of alarm indication and alarm output relay when you execute an

alarm ACK operation, see below.