Contents>> <<index – Yokogawa Touch Screen GP20 User Manual

Page 436

Advertising
background image

11

<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2012-2013, Yokogawa Electric Corporation

GS 04L52B01-01EN

May. 7, 2013-00

Continued

Input Type

Range

Measurement accuracy (digital display)

Max. resolution

of digital display

A/D integration time: 16.7ms or more

A/D integration time: 1.67ms (fast sampling mode)

RTD

Pt100

-200.0

to

850.0 °C

±(0.15 % of rdg + 0.3 °C)

±(0.3 % of rdg + 1.5 °C)

0.1 °C

-150.00 to

150.00 °C

0.01 °C

JPt100

-200.00 to

550.00 °C

0.1 °C

-150.00 to

150.00 °C

0.01 °C

Cu10 GE

-200.0

to

300.0 °C

±(0.2 % of rdg + 2.0 °C)

guaranteed range

Cu10 GE: -70.0 to 170.0 °C

Cu10 L&N: -75.0 to 150.0 °C

Cu10 WEED: -200.0 to 260.0 °C

Other range: -200.0 to 300.0 °C

±(0.4 % of rdg + 6.0 °C)

guaranteed range

Cu10 GE: -70.0 to 170.0 °C

Cu10 L&N: -75.0 to 150.0 °C

Cu10 WEED: -200.0 to 260.0 °C

Other range: -200.0 to 300.0 °C

0.1 °C

Cu10 L&N

-200.0

to

300.0 °C

Cu10 WEED

-200.0

to

300.0 °C

Cu10 BAILEY

-200.0

to

300.0 °C

Cu10 (20 °C)

alpha=0.00392

-200.0

to

300.0 °C

Cu10 (20 °C)

alpha=0.00393

-200.0

to

300.0 °C

Cu25 (0 °C)

alpha=0.00425

-200.0

to

300.0 °C

±(0.3 % of rdg + 0.8 °C)

±(0.5 % of rdg + 3.0 °C)

0.1 °C

Cu53 (0 °C)

alpha=0.00426035

-50.0

to

150.0 °C

±(0.15 % of rdg + 0.8 °C)

±(0.3 % of rdg + 4.0 °C)

0.1 °C

Cu100 (0 °C)

alpha=0.00425

-50.0

to

150.0 °C

±(0.2 % of rdg + 1.0 °C)

±(0.4 % of rdg + 5.0 °C)

0.1 °C

J263B

0.0

to

300.0 K

±1.0 K

Less than 40.0 K: ±3.0 K

±3.0 K

Less than 40.0 K: ±9.0 K

0.1 K

Ni100 (SAMA)

-200.0

to

250.0 °C

±(0.15 % of rdg + 0.4 °C)

±(0.3 % of rdg + 2.0 °C)

0.1 °C

Ni100 (DIN)

-60.0

to

180.0 °C

Ni120

-70.0

to

200.0 °C

Pt25

-200.0

to

550.0 °C

±(0.15 % of rdg + 0.8 °C)

±(0.3 % of rdg + 4.0 °C)

0.1 °C

Pt50

-200.0

to

550.0 °C

±(0.3 % of rdg + 0.6 °C)

±(0.6 % of rdg + 3.0 °C)

0.1 °C

Pt200 WEED

-100.0

to

250.0 °C

Cu10 GOST

-200.0

to

200.0 °C

±(0.2 % of rdg + 2.0 °C)

±(0.4 % of rdg + 6.0 °C)

0.1 °C

Cu50 GOST

-200.0

to

200.0 °C

±(0.15 % of rdg + 0.6 °C)

±(0.3 % of rdg + 4.0 °C)

0.1 °C

Cu100 GOST

-200.0

to

200.0 °C

±(0.15 % of rdg + 0.3 °C)

±(0.3 % of rdg + 1.5 °C)

0.1 °C

Pt46 GOST

-200.0

to

550.0 °C

±(0.3 % of rdg + 0.8 °C)

±(0.6 % of rdg + 4.0 °C)

0.1 °C

Pt100 GOST

-200.0

to

600.0 °C

±(0.15 % of rdg + 0.3 °C)

±(0.3 % of rdg + 2.0 °C)

0.1 °C

DI

Level

Threshold level (Vth=2.4 V) Accuracy: ±0.1 V

-

Contact

Less than 1 kΩ: 1(ON), More than 100 kΩ: 0(OFF) (parallel capacitance of 0.01 μF or less)

-

Measurement accuracy at scaling: measurement accuracy at scaling (digits) = measurement accuracy (digits) x scaling

span (digits)/measurement span (digits) + 2 digits

* Rounding up decimal places

• Burnout detection: Burnout upscale, downscale,

or OFF selectable (for each channel).

Available input: TC, RTD, Standard signal

TC; Normal: 2 kΩ or less., Burnout: 200 kΩ

or more (parallel capacitance of 0.01 μF or

less)

Detection current: Approx. 10 μA

RTD; Normal: wiring resistance or less,

Burnout: 200 kΩ or more (parallel

capacitance of less than 0.01 μF or less)

Standard signal: Normal: Within measuring

range, Burnout: -10% or less or 110% or

more of the specified span.

• Input external resistance:

DC voltage, thermocouple input: 2 kΩ or

below

Resistance temperature detector input: 10 Ω

or below in each wire (Same resistance in

three wires)

• Input bias current: ±10 nA or less (when burnout

function does not work)

• Measured current (for RTD): Approx. 1 mA

• Input resistance:

10 MΩ or more for TC/DC voltage (1 V range or

less) input

Approx. 1 MΩ for DC voltage (2 V range or

more)/standard signal input

• Allowable signal source resistance: 2 kΩ or less

for TC/DC voltage (1 V range or less) input

• Effect of signal source resistance:

±10 μV/1kΩ or less for TC/DC voltage (1 V range

or less) input

±0.15 %/1kΩ or less for DC voltage (2 V range or

more)/standard signal input

• Allowable wiring resistance: Max. 10 Ω per line

for RTD input (conductor resistance between the

three lines shall be equal)

• Effect of wiring resistance: ±0.1°C/10 Ω for RTD

input (conductor resistance between the three

lines shall be equal)

• Allowable input voltage:

±10 V DC for TC/DC voltage (1 V range or less)/

RTD/DI input

±60 V DC for DC voltage (2 V range or more) input

Advertising
This manual is related to the following products: