2 setting expressions, Setting expressions -49, App 1.5.2 setting expressions – Yokogawa Touch Screen GP20 User Manual

Page 63: Math range

Advertising
background image

1-49

IM 04L51B01-01EN

Configuring the GX/GP

1

2

3

4

5

App

1.5.2

Setting Expressions

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu Math channel settings >

Calculation expression

Web browser:

Config. tab > Math channel settings > Math channel settings > Channel

range (display example: A001-A020)

Hardware configurator:

Math channel settings > Math channel settings >Channel range

(display example:A001-A020)

Description

Setup Item

Selectable Range or Options

Default Value

First-CH

GX20/GP20: A001 to A100

GX10/GP10: A001 to A050

A001

Last-CH

Same as the first channel

A001

First-CH, Last-CH

Set the target channels.

Math range

Setup Item

Selectable Range or Options

Default Value

On/Off

Off, On

Off

Calculation expression

1

Character string (up to 120 characters)

001

Decimal place

1

0, 1, 2, 3, 4, 5

2

Span Lower

1

–9999999 to 99999999

0.00

Span Upper

1

–9999999 to 99999999

100.00

Unit

1

Character string (up to 6 characters,

A a # 1

)

1 Appears when On/Off is set to

On.

On/Off

Set the channels that you want to use to

On.

Computation is performed every scan interval, starting with the smallest channel number.

Example: If you specify A002=A001+A003, the value of the previous scan interval is used for

A003.

Calculation expression

Set the expression.

In computations, measured values are handled as values without units. For example, if the

measured data from channel 0001 is 20 mV and the measured data from channel 0002 is

20 V, the computed result of 0001 + 0002 is 40.

1.5 Configuring Math Channels

Advertising
This manual is related to the following products: