2 troubleshooting, 1 messages, Troubleshooting -9 – Yokogawa Touch Screen GP20 User Manual

Page 363: Messages -9

Advertising
background image

5-9

IM 04L51B01-01EN

Maintenance and T

roubleshooting

1

2

3

4

5

App

5.2 Troubleshooting

5.2.1

Messages

Error codes and messages may appear on the screen while you are using the GX/GP. A list

of the possible error codes and messages are given in the table below. Communication error

codes and messages are also listed.

Errors Related to Parameter Settings

• Setting Errors

Code

Message

Description, Corrective Action, Ref. Section

1

Incorrect date or time setting.

Enter a correct value.

2

The setting of the parameter is wrong Please confirm

specifications.

Check the communication command specifications.

3

The input numerical value exceeds the set range.

Enter a proper value.

4

Incorrect input character string.

Enter a proper character string.

5

Too many characters.

Enter the correct number of characters.

6

The format of the parameter is wrong.

Check the communication command specifications.

7

There is no character string saved in the clipboard.

Copy a character string to the clipboard.

8

The character string saved in the clipboard is too long.

Paste a character string with the specified number of

characters.

9

String’s length has exceeded.

Enter the correct number of characters.

11

The module does not exist.

Check that the module is installed correctly.

12

There is no specified input channel.

Specify a channel that is installed.

13

Exceeded the number of channels which can be set.

Set the correct number of channels.

14

Use the same channel more than twice.

Set a channel only once.

15

The specified number is set to manual.

Set the DO channel or internal switch

Type to Alarm.

16

Please specify at least one channel.

Specify a channel.

31

Measured value is incorrect. (in ascending order)

Set the calibration correction value to a value greater

than the previous value.

41

There is no channel specified by the MATH expression.

Check the channel number specified by the expression.

42

MATH expression grammar is incorrect.

Check that the expression grammar is correct.

43

Invalid order of operators.

Check that the operator used in the expression in

relation to the applicable operands meets the grammar

requirements.

44

Too many operators for MATH expression.

The maximum number of operators in an expression has

been exceeded.

Reduce the number of operators, such as by splitting up

the expression into multiple math channels.

45

Nonexistent constant specified in MATH expression.

Check the constant number specified by the expression.

91

This username is already registered.

Register another user name.

92

’quit’ string cannot be specified.

Change the character string.

93

String including space cannot be specified.

Change the character string.

94

NULL cannot be specified.

Change the character string.

101

This port number is already in use. Please enter a different

number.

Enter a different port number for each function.

102

IIP address doesn’t belong to class A, B, or C.

Check the IP address.

103

The result of the masked IP address is all 0s or 1s.

Check the subnet mask.

104

SUBNET mask is incorrect.

Check the subnet mask.

105

The net part of default gateway is not equal to that of IP address. Check the IP address.

106

More than one address cannot be specified.

Only a single sender is allowed.

107

Number entered exceeds channel number range. Use another

command.

Check the syntax of the Modbus command.

Advertising