Bl-1031, Bl-1032, Bl-1033 – Brocade Fabric OS Message Reference (Supporting Fabric OS v7.3.0) User Manual
Page 210

188
Fabric OS Message Reference
53-1003140-01
BL-1031
5
BL-1031
Message
Link timeout in internal port (slot <slot number>, port <port number>) resulted in
blade fault. Use slotpoweroff/slotpoweron to recover the blade.
Message Type
LOG
Severity
CRITICAL
Probable Cause
Indicates that link timeout occurred in one of the back-end internal ports.
Recommended
Action
Power cycle the blade using the slotPowerOff and slotPowerOn commands.
BL-1032
Message
(slot <slot number>,bitmap 0x<object control flags(bitmap)>) ports never came up
ONLINE (reason <reason for port disable>, state <status of the blade>). Disabling
slot.
Message Type
LOG
Severity
CRITICAL
Probable Cause
Indicates that back-end (non-user) ports have not come online within the time limit.
Recommended
Action
Execute the diagPost command to make sure that Power-On Self-Test (POST) is enabled; then power
cycle the blade using the slotPowerOff and slotPowerOn commands or have the blade's ejector switch
cycled to run POST and verify that the blade does not have any hardware problems.
If the message persists, replace the blade.
BL-1033
Message
(slot <slot number>,bitmap 0x<object control flags(bitmap)>) No disable
acknowledgment from ports (state <status of the blade>). Disabling slot.
Message Type
LOG
Severity
CRITICAL
Probable Cause
Indicates that the system has timed out waiting for the disable messages from the user ports after
disabling the ports.
Recommended
Action
Execute the diagPost command to make sure that Power-On Self-Test (POST) is enabled; then power
cycle the blade using the slotPowerOff and slotPowerOn commands or have the blade's ejector switch
cycled to run POST and verify that the blade does not have any hardware problems.
If the message persists, replace the blade.