Safety engineering

Safe parameter setting
Parameter setting

1

l

102

EDS94AYAE EN 7.0

1.6.1.2

Parameter set transfer from the memory module

The safe parameter set transfer is supported by a safe parameter set stored in the memory
module, e.g. in case of a module exchange.

ƒ

A valid parameter set with a corresponding module ID must be stored.

ƒ

The safety module must be in the service status.

The transfer of the parameter set from the memory module must be acknowledged at the
safety module.

ƒ

The "MS" LED is flashing (safety module is in service status.)

ƒ

"AS" LED is lit

ƒ

Press module switch S82 and keep it pressed

ƒ

"AS" LED starts blinking

ƒ

When the "AS" LED goes off, release the S82 module switch immediately

ƒ

The "AS" LED is lit again after a short time

ƒ

Press again the S82 module switch and keep it pressed

ƒ

"AS" LED starts blinking

ƒ

When the "AS" LED goes off, release the S82 module switch immediately

ƒ

The parameter set transfer is completed successfully.

If system−related response times (approx. 2.5 s) cannot be complied with, the parameter
transfer is cancelled. The process must be started again.

In case of success, the parameter transfer is recorded in the logbook of the standard device
and the service status is quit by a software restart.

If the parameter set is invalid, an error is indicated and the "ME" LED is blinking.

t

t

max

t

max

t

max

AS

S82

0

0

I

I

SM301DIA_P

Fig. 1−13

Acknowledgement procedure

AS

AS light−emitting diode

S82

S82 module switch

t

Time axis

t

max

Maximum permissible response time