Safety engineering

Safety functions

Safely limited speed

1

l

73

EDS94AYAE EN 7.0

Index:

Data type:

Name:

Parameter:

C15333

SLS: Permissible direction of movement

UNSIGNED_8

9242

d

= 241A

h

Permissible direction of movement during SLS monitoring

Selection list

(Lenze setting printed in bold)

Information

0 Both directions enabled

1 Positive direction enabled

2 Negative direction enabled

Subcodes

Information

C15333/1

SLS1: Permissible direction of movement

(from SM301

V1.3)

C15333/2

SLS2: Permissible direction of movement

(from SM301

V1.3)

C15333/3

SLS3: Permissible direction of movement

(from SM301

V1.3)

C15333/4

SLS4: Permissible direction of movement

(from SM301

V1.3)

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15350

SLS, SMS: Max. response time

UNSIGNED_16

9225

d

= 2409

h

Maximum time after an exceeded speed has been detected, after which the speed must be below the limit
again.

Setting range

(min. value | unit | max. value)

Information

0

MS

30000 Lenze: 0, increment: 2 ms

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

1.3.9.2

Activation

How to activate the function:

ƒ

"OFF state" at a safe input, the function of which has been assigned by parameter
setting.

ƒ

Via a safety bus data telegram with corresponding content.

1.3.9.3

Fault analysis

The fault analysis is described with the SMS function (

69).