Safety engineering, Safety functions safe stop 2, Codes – Lenze E94AYAE SM301 User Manual

Page 63: 2 activation how to activate the function, As response to the error stop request

Advertising
background image

Safety engineering

Safety functions

Safe stop 2

1

l

63

EDS94AYAE EN 7.0

Codes

Parameter:

Name:

Data type:

Index:

C15300

Restart behaviour

UNSIGNED_8

9275

d

= 243B

h

Behaviour for restart after functions have been cancelled

Selection list

(Lenze setting bold)

Information

0 Acknowledged restart

1 Automatic restart

Subcodes

Information

C15300/1

Restart - STO, SS1

C15300/2

Restart - SS2, SOS

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15305

SS1, SS2: Stopping time

UNSIGNED_16

9270

d

= 2436

h

Stopping time for the SS1 and SS2 safety functions

Setting range

(min. value | unit | max. value)

Information

0

MS

30000 Lenze: 0, increment: 2 ms

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15308

SS2 mode

UNSIGNED_8

9267

d

= 2433

h

Selection whether SS2 is to be executed already after reaching n=0 SOS or only after reaching the parameterised
stopping time.

Selection list

(Lenze setting bold)

Information

0 SOS after stopping time

(As of SM301 V1.3)

1 SOS at n = 0

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15310

Tolerance window (n=0)

INTEGER_16

9265

d

= 2431

h

Safely monitored tolerance window for zero speed

Setting range

(min. value | unit | max. value)

Information

0

rpm

16000 Lenze: 0

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15311

SOS: Tolerance window (Delta p=0)

UNSIGNED_32

9264

d

= 2430

h

Safely monitored tolerance window for zero position change

Display area

(min. value | unit | max. value)

Information

0

Incr.

327680 Lenze: 0

(From SM301 V1.3)

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15312

SOS: Maximum change in position

UNSIGNED_32

9263

d

= 242F

h

Amount of the maximum change in position while SOS was active

Display area

(min. value | unit | max. value)

Information

0

Incr.

2147483647

(From SM301 V1.3)

þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer

1.3.5.2

Activation

How to activate the function:

ƒ

"OFF state" at a safe input, the function of which has been assigned by parameter
setting.

ƒ

Via a safety bus data telegram with corresponding content.

ƒ

As response to the error stop request.

Advertising