Safety engineering, Appendix module internal codes – Lenze E94AYAE SM301 User Manual

Page 117

Advertising
background image

Safety engineering

Appendix

Module internal codes

1

l

117

EDS94AYAE EN 7.0

Index:

Data type:

Name:

Parameter:

C15035

CAS: Cascading

UNSIGNED_8

9540

d

= 2544

h

Safe cascading

Selection list

(Lenze setting bold)

Information

0 No cascading

(As of SM301 V1.1)

4 Cascading with SD−In4

þ Read access } Write access o CINH o PLC-STOP o No transfer

C15036

CAS: Stop delay

UNSIGNED_16

9539

d

= 2543

h

Circulation time of safe cascading

Display area

(min. value | unit | max. value)

Information

0

MS

65535

(As of SM301 V1.1)

l

Display of the time that passes from switching the
SD−Out1 output to OFF state to the detection of the
OFF state at the SD−In4 input. This information may
be helpful for system commissioning/maintenance.

l

If "0 ms" is displayed after a stop, another safety
module has activated the stop via the cascade.

l

The time is displayed until the next system
acknowledgement.

þ Read access o Write access o CINH o PLC-STOP o No transfer

C15040

Input image

BITFIELD_32

9535

d

= 253F

h

Input image of the external module inputs of the safety module, shown in channels.

Value is bit coded:

Information

Bit 0 SD-In1 channel A

Safe input 1

Bit 1 SD-In1 channel B

Bit 2 SD-In2 channel A

Safe input 2

Bit 3 SD-In2 channel B

Bit 4 SD-In3 channel A

Safe input 3

Bit 5 SD-In3 channel B

Bit 6 SD-In4 channel A

Safe input 4

Bit 7 SD-In4 channel B

Bit 8 reserved

...

Bit 15 reserved

Bit 16 AIE

AIE input (fault acknowledgement)

Bit 17 AIS

AIS input (restart acknowledgement)

Bit 18 Module switch

Bit 19 reserved

...

Bit 31 reserved

þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer