Safety engineering

Device modules

Safe output

1

l

37

EDS94AYAE EN 7.0

1.2.5

Safe output

1.2.5.1

General

Via the safe output O1A/O1B information can be output to a higher−level unit (e.g. safety
PLC) or external switching elements (actuators) can be controlled.

The feedback output is designed in a potential−free fashion. If electrical isolation is
required, a separate supply line must be used.

ƒ

The status of the safe output is controlled via two ways:
– directly from the safety module (parameter setting required)
– via the PROFIsafe output data

ƒ

The safe output is PP switching, i.e. two plus channels are switched.

ƒ

The safe output in ON state is cyclically tested by quick LOW switching.
– The A and B channels are tested at different times in cycles of approx. 2 s, with

test pulses of < 1 ms.

– When selecting the downstream control elements, ensure that the test pulses will

not be detected as LOW signal.

These errors will be detected and set the output to OFF state:

ƒ

Short circuit to supply voltage.

ƒ

In the ON state: Short circuit between the output signals.

ƒ

IN the OFF state: Missing 24−V supply voltage at the terminal 24O is detected as
"Stuck−at−Low" error.

These errors are not detected:

ƒ

In the OFF state: short circuit between the output signals.

The output can be assigned multiple feedback information by parameter setting:

ƒ

Status of the safety function

ƒ

Information on error responses

The code C15060 contains information on the status of the feedback output.

Additional conditions for SM301 from version VB 1.1 onwards:

ƒ

With active cascading in C15035 the SD−Out1 output cannot be used freely
anymore.