Safety engineering

Safety functions

Cascading

1

l

87

EDS94AYAE EN 7.0

1.3.13.2

Conditions

ƒ

This function is available from SM301 V1.1.

ƒ

The SD−In4 input must be parameterised as active input for the "emergency stop"
function and the input delay for SD−In4 must be

£ 10 ms.

ƒ

The emergency stop function to be executed must be parameterised as STO via the
"SSE: emergency stop function" parameter.

ƒ

The restart behaviour of the drive after the STO/SS1 stop function has been
executed must be parameterised to "Acknowledged restart".

ƒ

The control of the SD−Out1 output via a possibly parameterised safety bus must be
inhibited.

ƒ

The SS1 mode (C15306) must be set to "STO after stopping time".

ƒ

The plausibility check rejects other settings until they are parameterised correctly.

Codes

Parameter:

Name:

Data type:

Index:

C15035

CAS: Cascading

UNSIGNED_8

9540

d

= 2544

h

Safe cascading

Selection list

(Lenze setting bold)

Information

0 No cascading

(As of SM301 V1.1)

4 Cascading with SD−In4

þ Read access } Write access o CINH o PLC-STOP o No transfer

C15036

CAS: Stop delay

UNSIGNED_16

9539

d

= 2543

h

Circulation time of safe cascading

Display area

(min. value | unit | max. value)

Information

0

MS

65535

(As of SM301 V1.1)

l

Display of the time that passes from switching the
SD−Out1 output to OFF state to the detection of the
OFF state at the SD−In4 input. This information may
be helpful for system commissioning/maintenance.

l

If "0 ms" is displayed after a stop, another safety
module has activated the stop via the cascade.

l

The time is displayed until the next system
acknowledgement.

þ Read access o Write access o CINH o PLC-STOP o No transfer

1.3.13.3

Activation

The cascade trips with every STO, irrespective of which safety module adopts the STO
status and for which reason.