Safety engineering
Safety functions
Cascading
l
87
EDS94AYAE EN 7.0
1.3.13.2
Conditions
ƒ
This function is available from SM301 V1.1.
ƒ
The SD−In4 input must be parameterised as active input for the "emergency stop"
function and the input delay for SD−In4 must be
£ 10 ms.
ƒ
The emergency stop function to be executed must be parameterised as STO via the
"SSE: emergency stop function" parameter.
ƒ
The restart behaviour of the drive after the STO/SS1 stop function has been
executed must be parameterised to "Acknowledged restart".
ƒ
The control of the SD−Out1 output via a possibly parameterised safety bus must be
inhibited.
ƒ
The SS1 mode (C15306) must be set to "STO after stopping time".
ƒ
The plausibility check rejects other settings until they are parameterised correctly.
Codes
Parameter:
Name:
Data type:
Index:
C15035
CAS: Cascading
UNSIGNED_8
9540
d
= 2544
h
Safe cascading
Selection list
(Lenze setting bold)
Information
0 No cascading
(As of SM301 V1.1)
4 Cascading with SD−In4
þ Read access } Write access o CINH o PLC-STOP o No transfer
C15036
CAS: Stop delay
UNSIGNED_16
9539
d
= 2543
h
Circulation time of safe cascading
Display area
(min. value | unit | max. value)
Information
0
MS
65535
(As of SM301 V1.1)
l
Display of the time that passes from switching the
SD−Out1 output to OFF state to the detection of the
OFF state at the SD−In4 input. This information may
be helpful for system commissioning/maintenance.
l
If "0 ms" is displayed after a stop, another safety
module has activated the stop via the cascade.
l
The time is displayed until the next system
acknowledgement.
þ Read access o Write access o CINH o PLC-STOP o No transfer
1.3.13.3
Activation
The cascade trips with every STO, irrespective of which safety module adopts the STO
status and for which reason.