Safety engineering, Appendix module internal codes – Lenze E94AYAE SM301 User Manual

Page 123

Advertising
background image

Safety engineering

Appendix

Module internal codes

1

l

123

EDS94AYAE EN 7.0

Index:

Data type:

Name:

Parameter:

C15202

OMS: Function at LOW level

UNSIGNED_8

9373

d

= 249D

h

Function that is executed in case of LOW level at the safe input with OMS function.
Caution: According to the closed−circuit principle, the parameterisation must not cause any additional danger.

Selection list

(read only)

Information

0 Normal operation

(From SM301 V1.3)

1 Special operation

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15203

SLI: Safely lim. increment

UNSIGNED_32

9372

d

= 249C

h

Number of increments for safely limited increment

Setting range

(min. value | unit | max. value)

Information

0

Incr.

2147483647 Lenze: 1, deactivate: 0

(From SM301 V1.4)

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15204

SLI: Amount of position change

UNSIGNED_32

9371

d

= 249B

h

Maximum position change while SLI is active.

Display area

(min. value | unit | max. value)

Information

0

Incr.

2147483647

(From SM301 V1.4)

þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer

C15205

SSE: Safe stop emergency function

UNSIGNED_8

9370

d

= 249A

h

Selection of the stop function for emergency stop

Selection list

(Lenze setting printed in bold)

Information

0 STO

Safe torque off

1 SS1

Safe stop 1

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15300

Restart behaviour

UNSIGNED_8

9275

d

= 243B

h

Behaviour for restart after functions have been cancelled

Selection list

(Lenze setting bold)

Information

0 Acknowledged restart

1 Automatic restart

Subcodes

Information

C15300/1

Restart - STO, SS1

C15300/2

Restart - SS2, SOS

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15305

SS1, SS2: Stopping time

UNSIGNED_16

9270

d

= 2436

h

Stopping time for the SS1 and SS2 safety functions

Setting range

(min. value | unit | max. value)

Information

0

MS

30000 Lenze: 0, increment: 2 ms

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15306

SS1 mode

UNSIGNED_8

9269

d

= 2435

h

Selection list

(Lenze setting bold)

Information

0 STO after stopping time

(From SM301 V1.3)

1 STO at n = 0

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15307

SS1: Deceleration STO after n=0

UNSIGNED_16

9268

d

= 2434

h

Display area

(min. value | unit | max. value)

Information

0

ms

30000 Lenze: 0, increment: 2 ms

(From SM301 V1.3)

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer