Safety engineering

Safety functions
Safe operation mode selector

1

l

82

EDS94AYAE EN 7.0

Codes

Parameter:

Name:

Data type:

Index:

C15200

OMS: Stop function

UNSIGNED_8

9375

d

= 249F

h

Selection of the stop function in special operation

Selection list

(Lenze setting bold)

Information

0 STO

Safe torque off

1 SS1

Safe stop 1

2 SS2

Safe stop 2

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15201

OMS: motion function

UNSIGNED_8

9374

d

= 249E

h

Selection of the motion function in special operation

Selection list

(Lenze setting bold)

Info

3 SLS1

Safely limited speed 1

(Lenze setting up to SM301 V1.3)

4 SLS2

Safely limited speed 2

(From SM301 V1.1)

5 SLS3

Safely limited speed 3

(From SM301 V1.1)

6 SLS4

Safely limited speed 4

(as of SM301 V1.1)

11 Free traversing

(Lenze setting from SM301 V1.4)

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

I

Tip!

If SLSx has been parameterised as the motion function during special
operation, a change to the acceptance operation is not possible until the
reduced speed is monitored and maintained (SLSx monitored).

C15202

OMS: Function at LOW level

UNSIGNED_8

9373

d

= 249D

h

Function that is executed in case of LOW level at the safe input with OMS function.
Caution: According to the closed−circuit principle, the parameterisation must not cause any additional danger.

Selection list

(read only)

Information

0 Normal operation

(From SM301 V1.3)

1 Special operation

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15203

SLI: Safely lim. increment

UNSIGNED_32

9372

d

= 249C

h

Number of increments for safely limited increment

Setting range

(min. value | unit | max. value)

Information

0

Incr.

2147483647 Lenze: 1, deactivate: 0

(From SM301 V1.4)

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15204

SLI: Amount of position change

UNSIGNED_32

9371

d

= 249B

h

Maximum position change while SLI is active.

Display area

(min. value | unit | max. value)

Information

0

Incr.

2147483647

(From SM301 V1.4)

þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer