Safety engineering, Safe bus interfaces profisafe connection – Lenze E94AYAE SM301 User Manual

Page 98

Advertising
background image

Safety engineering

Safe bus interfaces
PROFIsafe connection

1

l

98

EDS94AYAE EN 7.0

Status byte

For the PROFIsafe V1 mode only the indicated bits of the PROFIsafe status byte are
supported:

Assignment

Bit

Byte

7

6

5

4

3

2

1

0

4

FV_activated

COM−Failure WD-Timeout

COM−Failure CRC

Tab. 1−13

Structure of the PROFIsafe status byte in V1 mode

Bit coding − status byte

Bit

Name

Description

2

COM−Failure CRC

Status after communication error is active.

3

COM−Failure
WD-Timeout

Status after time−out is active.

4

FV_activated

The PROFIsafe input data is deactivated.

Reserved for future extensions

Tab. 1−14

Detailed specification of the status byte in V1 mode

For the PROFIsafe V2 mode only the indicated bits of the PROFIsafe status byte are
supported:

Assignment

Bit

Byte

7

6

5

4

3

2

1

0

4

cons_nr_R

Toggle_d

FV_activated

WD_timeout

CE_CRC

Tab. 1−15

Structure of the PROFIsafe status byte in V2 mode

Bit coding − status byte

Bit

Name

Description

2

CE_CRC

Status after communication error is active.

3

WD_timeout

Status after time−out is active.

4

FV_activated

The PROFIsafe input data is deactivated.

5

Toggle_d

Change shows increase of the consecutive number.

6

cons_nr_R

Consecutive number has been reset.

Reserved for future extensions

Tab. 1−16

Detailed specification of the status byte in V2 mode