Safety engineering – Lenze E94AYAE SM301 User Manual

Page 33

Advertising
background image

Safety engineering

Device modules

Safe inputs

1

l

33

EDS94AYAE EN 7.0

Index:

Data type:

Name:

Parameter:

C15034

SD-In input delay

UNSIGNED_8

9541

d

= 2545

h

Time between the recognition of the signal change and the effective evaluation of an input signal. As a result,
multiple and short signal changes due to contact bounce of the components are not taken into account.

Setting range

(min. value | unit | max. value)

Information

0

MS

100 Lenze: 0, increment: 2 ms

Subcodes

Information

C15034/1

Input delay SD-In1

C15034/2

Input delay SD-In2

C15034/3

Input delay SD-In3

C15034/4

Input delay SD-In4

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

Contact function test

)

Note!

Make sure that an internal contact function test is carried out at the safe
inputs:
Safe input in the ON state

ƒ

A LOW level at one channel puts the input in the OFF state. The discrepancy
monitoring starts simultaneously.

ƒ

A LOW level must be detected at both channels within the discrepancy time,
otherwise a discrepancy error will be reported.

ƒ

To be able to acknowledge the discrepancy error, a LOW level must be
detected before at both channels.

Safe input in the OFF state

ƒ

A HIGH level at one channel starts the discrepancy monitoring.

ƒ

A HIGH level must be detected at both channels within the discrepancy
time, otherwise a discrepancy error will be reported.

ƒ

To be able to acknowledge the discrepancy error, a HIGH level must be
detected before at both channels.

Switch both channels

to ON state

Switch both channels

to OFF state

One channel in

ON state

One channel in

OFF state

Value of safe input:

OFF state

Value of safe input:

OFF state

Value of safe input:

OFF state

Value of safe input:

ON state

Discrepancy monitoring

Discrepancy monitoring

OFF state

ON state