Safety engineering – Lenze E94AYAE SM301 User Manual

Page 93

Advertising
background image

Safety engineering

Safe bus interfaces

PROFIsafe connection

1

l

93

EDS94AYAE EN 7.0

Control byte

For the PROFIsafe V1 mode only the indicated bits of the PROFIsafe control byte are
supported:

Assignment

Bit

Byte

7

6

5

4

3

2

1

0

4

activate_FV

Tab. 1−8

Structure of the PROFIsafe control byte in V1 mode

Bit coding − control byte

Bit

Name

Value

Description

4

activate_FV

1

The PROFIsafe output data is passivated.

0

Reserved for future extensions

Tab. 1−9

Detailed specification of the control byte in V1 mode

For the PROFIsafe V2 mode only the indicated bits of the PROFIsafe control byte are
supported:

Assignment

Bit

Byte

7

6

5

4

3

2

1

0

4

Toggle_h

activate_FV

R_cons_nr

Tab. 1−10

Structure of the PROFIsafe control byte in V2 mode

Bit coding − control byte

Bit

Name

Value

Description

2

R_cons_nr

1

Reset of the consecutive number.

4

activate_FV

1

The PROFIsafe output data is passivated.

5

Toggle_h

1/0

Change increases the consecutive number.

0

Reserved for future extensions

Tab. 1−11

Detailed specification of the control byte in V2 mode

Control data filter

Unused functions in the control data of the safety bus must be set to "Inhibit" via the
parameter "S−bus: Control data filter" (C15113). After this, the functions can no longer be
activated via the safety bus independently of the transferred control data. As of
SM301 V1.2, the filtered control data is indicated in "S−bus: Display of control data"
(C15115).

1
0
1
0

a
a

i
i

1
0
1
1

0

1

2

SSP94SM301

Fig. 1−12

Function example − filter

0 Control data, incoming (0 = active, 1 = inactive)

1 Control data filter

(Selection in the »Engineer«: a = "pass through", i = "inhibit")

2 Effective control data (0 = active, 1 = inactive)