Safety engineering

Safe bus interfaces

PROFIsafe connection

1

l

91

EDS94AYAE EN 7.0

1.5.1.2

Description

Addressing

In order that a data telegram reaches the correct node, an unambiguous PROFIsafe target
address is required. If PROFIsafe has been selected as safety bus, the safety address is
simultaneously accepted as PROFIsafe target address. This address must comply with the
corresponding configuration of the safety PLC.

PROFIsafe frame

The PROFIsafe message is sent in the first slot of a PROFIBUS data telegram or in the second
slot of a PROFINET data telegram.

This must be observed for the hardware configuration of the safety PLC!

PROFIBUS data telegram

Header

PROFIsafe data

Data

Trailer

Slot 1

Slot 2

PROFINET data telegram

(as of SM301 V1.1)

Header

PROFIsafe data

Data

Trailer

Slot 2

Slot 1

PROFIsafe data

In the PROFIsafe data one bit each is used to control a certain safety function.

ƒ

The structure of the PROFIsafe message is described in the PROFIsafe profile.

ƒ

The length of the PROFIsafe message in the SM301 is eight bytes (fixed).

The PROFIsafe messages are structured according to the following system:

PROFIsafe message − V1 mode

Bit offset

Byte offset

7

6

5

4

3

2

1

0

0

PROFIsafe process data

PROFIsafe output data/PROFIsafe input data

1

2

3

4

Control byte or status byte

5

Consecutive number

6

CRC2

(Signature consists of PROFIsafe process data and PROFIsafe parameters)

7