Safety engineering

Safety functions
General information

1

l

50

EDS94AYAE EN 7.0

1.3.1.3

Restart

The restart behaviour of the drive can be parameterised (C15300).

ƒ

The "acknowledged restart" setting requires an acknowledgement to the safety
module. The acknowledgement is made via:
– Signal at the AIS input (with a signal time of 0.3 ... 10 s)
– Signal via the "PS_AIS" time (PROFIsafe)

ƒ

An error stop requires an acknowledgement (AIE), before the restart can be
acknowledged.

ƒ

The "Automatic restart" setting requires an acknowledgement at the master
control.

ƒ

With active cascading (C15035 as of SM301 V1.1) an "Automatic restart" after STO,
SS1 is not possible.

}

Danger!

When the request for the safety function is deactivated, the drive can restart
automatically. The behaviour can be set via the parameter "Restart behaviour"
(C15300/1/2).
In the case of an automatic restart, you must provide external measures which
ensure that the drive only restarts after an acknowledgement (EN 60204).

Codes

Parameter:

Name:

Data type:

Index:

C15300

Restart behaviour

UNSIGNED_8

9275

d

= 243B

h

Behaviour for restart after functions have been cancelled

Selection list

(Lenze setting bold)

Information

0 Acknowledged restart

1 Automatic restart

Subcodes

Information

C15300/1

Restart - STO, SS1

C15300/2

Restart - SS2, SOS

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer