Safety engineering

Safety functions
Safe maximum speed

1

l

68

EDS94AYAE EN 7.0

1.3.8

Safe maximum speed

1.3.8.1

Description

Safe Maximum Speed / SMS

This function monitors the maximum motor speed. If a value > 0 is indicated (C15320), the
function is activated.

If the maximum speed is exceeded, a error stop is caused. STO, SS1 or SS2 (C15321) can be
adjusted.

t

n

0

1

SM301DIA_SMS

1 Speed characteristic n of the motor

t

Time axis

Codes

Parameter:

Name:

Data type:

Index:

C15320

SMS: Max. speed Nmax

INTEGER_16

9255

d

= 2427

h

Selection of the maximum speed and activation of the SMS function

Setting range

(min. value | unit | max. value)

Information

0

rpm

16000 Lenze: 1, deactivate: 0

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15321

SMS: Response (n>Nmax)

UNSIGNED_8

9254

d

= 2426

h

Response to the exceeding of the set maximum speed

Selection list

(Lenze setting bold)

Information

0 STO

Safe torque off

1 SS1

Safe stop 1

2 SS2

Safe stop 2

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

C15350

SLS, SMS: Max. response time

UNSIGNED_16

9225

d

= 2409

h

Maximum time after an exceeded speed has been detected, after which the speed must be below the limit
again.

Setting range

(min. value | unit | max. value)

Information

0

MS

30000 Lenze: 0, increment: 2 ms

þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer

1.3.8.2

Activation

The function is activated or deactivated via the parameter value. A value > 0 activates the
function, a value = 0 deactivates the function.